UL Unarmored Tray Power | Multi-Conductor (2000V)
Tray Power cables are suitable for use in ventilated, non-ventilated and ladder type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp or dry locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and Commercial applications.
Construction
Voltage
2000V
Product Construction
-
- Insulation:
- FR XLPE (RHW-2 rated)rated: 90°C wet / dry
- Insulation:
-
- Jacket:
- FR PVC outer black jacket rated: 90°C to -40°C
- Thermoset CPE (optional)
- Thermoplastic CPE (optional)
- Thermoplastic LSZH (optional)
- Jacket:
- Available in:
- Custom insulation / jacket colors
- Composite constructions
Colour Coding
- Black conductors (standard)
- Optional:
- Method1 K1 or K2
Certifications
Certifications/Compliances
- UL 1277, Tray Cable (TC) (optional)CPE & LSZH only)
- UL 44, Thermoset Insulated Wires and Cables
- UL 1685 / FT4, Vertical Tray Flame Test rated
- IEEE 1202 / 383 (70,000 BTU / hr), Vertical Flame Test rated (optional)
- ICEA T-30-520 (70,000 BTU / hr), Vertical Flame Test rated
- XLPE (RHW-2 rated), 90°C wet / dry
- UV sunlight resistant SUN RES (all colours)
- Direct burial rated
- -40°C cold bend rated
- Rated for use in hazardous locations:
- Class I Zone 2 (Div 2)
- Class II Zone 22 (Div 2)
Properties
|
Part Number | Number of Conductors | Conductor Size (AWG/MCM) | Nominal Diameter Overall Cable (in/mm) | Cable Weight (lbs/1000ft)/ (kg/km) | Ampacity (30°C ambient) | Max. Pulling Tension (Pulling Eye) (lb/kg) | Min. Bend Radius (Pull) (in/mm) |
2K010U140200300 | 2 | 14 | 0.492 / 12.5 | 111 / 165 | 25 | 66 / 30 | 4.4 / 112 |
2K010U120200300 | 2 | 12 | 0.528 / 13.41 | 136 / 202 | 30 | 104 / 47 | 4.8 / 121 |
2K010U100200300 | 2 | 10 | 0.608 / 15.44 | 191 / 284 | 40 | 166 / 75 | 5.5 / 139 |
2K010U080200300 | 2 | 8 | 0.706 / 17.93 | 261 / 388 | 55 | 265 / 120 | 6.4 / 161 |
2K010U060200300 | 2 | 6 | 0.784 / 19.91 | 346 / 516 | 75 | 419 / 190 | 7.1 / 179 |
2K010U040200300 | 2 | 4 | 0.918 / 23.32 | 513 / 764 | 95 | 668 / 303 | 8.3 / 210 |
2K010U030200300 | 2 | 3 | 0.972 / 24.69 | 608 / 904 | 115 | 842 / 382 | 8.7 / 222 |
2K010U020200300 | 2 | 2 | 1.034 / 26.26 | 718 / 1069 | 130 | 1062 / 482 | 9.3 / 236 |
2K010U010240300 | 2 | 1 | 1.192 / 30.28 | 915 / 1362 | 145 | 1339 / 607 | 10.7 / 272 |
2K010U1/0240300 | 2 | 1/0 | 1.272 / 32.31 | 1100 / 1637 | 170 | 1690 / 766 | 11.4 / 291 |
2K010U2/0240300 | 2 | 2/0 | 1.358 / 34.49 | 1321 / 1966 | 195 | 2130 / 966 | 12.2 / 310 |
2K010U3/0240300 | 2 | 3/0 | 1.46 / 37.08 | 1594 / 2372 | 225 | 2671 / 1212 | 13.1 / 334 |
2K010U4/0240300 | 2 | 4/0 | 1.572 / 39.93 | 1932 / 2876 | 260 | 3386 / 1536 | 14.1 / 359 |
2K010U250260300 | 2 | 250 | 1.784 / 45.31 | 2366 / 3520 | 290 | 4000 / 1814 | 16.1 / 408 |
2K010U300260300 | 2 | 300 | 1.89 / 48.01 | 2754 / 4099 | 320 | 4800 / 2177 | 17 / 432 |
2K010U350260300 | 2 | 350 | 1.99 / 50.55 | 3138 / 4670 | 350 | 5600 / 2540 | 17.9 / 455 |
2K010U500260300 | 2 | 500 | 2.246 / 57.05 | 4259 / 6338 | 430 | 8000 / 3629 | 20.2 / 513 |
2K010U140300300 | 3 | 14 | 0.521 / 13.23 | 137 / 204 | 25 | 99 / 45 | 4.7 / 119 |
2K010U120300300 | 3 | 12 | 0.59 / 14.98 | 189 / 282 | 30 | 157 / 71 | 5.3 / 135 |
*Ampacity value based on National Electrical Code, Version 2020, Table 310.16. Values are corrected according to Table 310.15(C)(1) for number of Conductors. Per NEC 310.15(C)(1), the ampacity of 4/C cable shall be reduced by a factor of 0.8 when the neutral is considered a current-carrying conductor.
Part Number | Number of Conductors | Conductor Size (AWG/MCM) | Nominal Diameter Overall Cable (in/mm) | Cable Weight (lbs/1000ft)/ (kg/km) | Ampacity (30°C ambient) | Max. Pulling Tension (Pulling Eye) (lb/kg) | Min. Bend Radius (Pull) (in/mm) |
2K010U100300300 | 3 | 10 | 0.643 / 16.34 | 244 / 363 | 40 | 249 / 113 | 5.8 / 147 |
2K010U080300300 | 3 | 8 | 0.749 / 19.02 | 339 / 505 | 55 | 397 / 180 | 6.7 / 171 |
2K010U060300300 | 3 | 6 | 0.832 / 21.14 | 458 / 682 | 75 | 629 / 285 | 7.5 / 190 |
2K010U040300300 | 3 | 4 | 0.973 / 24.72 | 680 / 1012 | 95 | 1002 / 454 | 8.8 / 223 |
2K010U030300300 | 3 | 3 | 1.031 / 26.2 | 811 / 1207 | 115 | 1263 / 573 | 9.3 / 236 |
2K010U020300300 | 3 | 2 | 1.098 / 27.89 | 972 / 1446 | 130 | 1593 / 723 | 9.9 / 251 |
2K010U010340300 | 3 | 1 | 1.268 / 32.2 | 1235 / 1838 | 145 | 2009 / 911 | 11.4 / 290 |
2K010U1/0340300 | 3 | 1/0 | 1.354 / 34.39 | 1491 / 2219 | 170 | 2534 / 1150 | 12.2 / 310 |
2K010U2/0340300 | 3 | 2/0 | 1.446 / 36.74 | 1803 / 2684 | 195 | 3194 / 1449 | 13 / 331 |
2K010U3/0340300 | 3 | 3/0 | 1.556 / 39.52 | 2191 / 3261 | 225 | 4007 / 1818 | 14 / 356 |
2K010U4/0340300 | 3 | 4/0 | 1.676 / 42.58 | 2677 / 3984 | 260 | 5078 / 2304 | 15.1 / 383 |
2K010U250360300 | 3 | 250 | 1.9 / 48.25 | 3248 / 4833 | 290 | 6000 / 2722 | 17.1 / 434 |
2K010U300360300 | 3 | 300 | 2.014 / 51.15 | 3793 / 5645 | 320 | 7200 / 3266 | 18.1 / 460 |
2K010U350360300 | 3 | 350 | 2.121 / 53.88 | 4338 / 6456 | 350 | 8400 / 3810 | 19.1 / 485 |
2K010U500360300 | 3 | 500 | 2.396 / 60.87 | 5944 / 8846 | 430 | 12000 / 5443 | 21.6 / 548 |
2K010U750360300 | 3 | 750 | 2.906 / 73.81 | 8860 / 13185 | 535 | 18000 / 8165 | 26.2 / 664 |
2K010U140400300 | 4 | 14 | 0.601 / 15.27 | 188 / 280 | 20 | 132 / 60 | 5.4 / 137 |
2K010U120400300 | 4 | 12 | 0.645 / 16.37 | 235 / 349 | 24 | 209 / 95 | 5.8 / 147 |
2K010U100400300 | 4 | 10 | 0.705 / 17.9 | 306 / 456 | 32 | 332 / 151 | 6.3 / 161 |
2K010U080400300 | 4 | 8 | 0.823 / 20.9 | 427 / 636 | 44 | 529 / 240 | 7.4 / 188 |
2K010U060400300 | 4 | 6 | 0.956 / 24.28 | 617 / 917 | 60 | 839 / 380 | 8.6 / 219 |
2K010U040400300 | 4 | 4 | 1.069 / 27.16 | 869 / 1293 | 76 | 1336 / 606 | 9.6 / 244 |
2K010U030400300 | 4 | 3 | 1.134 / 28.81 | 1032 / 1535 | 92 | 1684 / 764 | 10.2 / 259 |
2K010U020400300 | 4 | 2 | 1.209 / 30.71 | 1246 / 1854 | 104 | 2124 / 964 | 10.9 / 276 |
2K010U010440300 | 4 | 1 | 1.399 / 35.54 | 1592 / 2369 | 116 | 2678 / 1215 | 12.6 / 320 |
2K010U1/0440300 | 4 | 1/0 | 1.496 / 37.99 | 1925 / 2864 | 136 | 3379 / 1533 | 13.5 / 342 |
2K010U2/0440300 | 4 | 2/0 | 1.6 / 40.63 | 2340 / 3483 | 156 | 4259 / 1932 | 14.4 / 366 |
2K010U3/0440300 | 4 | 3/0 | 1.782 / 45.27 | 2947 / 4385 | 180 | 5343 / 2423 | 16 / 407 |
2K010U4/0440300 | 4 | 4/0 | 1.917 / 48.7 | 3597 / 5352 | 208 | 6771 / 3071 | 17.3 / 438 |
2K010U250460300 | 4 | 250 | 2.1 / 53.35 | 4207 / 6261 | 232 | 8000 / 3629 | 18.9 / 480 |
2K010U300460300 | 4 | 300 | 2.228 / 56.6 | 4933 / 7342 | 256 | 9600 / 4355 | 20.1 / 509 |
2K010U350460300 | 4 | 350 | 2.349 / 59.66 | 5649 / 8407 | 280 | 11200 / 5080 | 21.1 / 537 |
2K010U500460300 | 4 | 500 | 2.657 / 67.49 | 7759 / 11547 | 344 | 16000 / 7258 | 23.9 / 607 |
*Ampacity value based on National Electrical Code, Version 2020, Table 310.16. Values are corrected according to Table 310.15(C)(1) for number of Conductors. Per NEC 310.15(C)(1), the ampacity of 4/C cable shall be reduced by a factor of 0.8 when the neutral is considered a current-carrying conductor.
Markets / Applications
|
|
Voltage
2000V
Product Construction
-
- Insulation:
- FR XLPE (RHW-2 rated)rated: 90°C wet / dry
- Insulation:
-
- Jacket:
- FR PVC outer black jacket rated: 90°C to -40°C
- Thermoset CPE (optional)
- Thermoplastic CPE (optional)
- Thermoplastic LSZH (optional)
- Jacket:
- Available in:
- Custom insulation / jacket colors
- Composite constructions
Colour Coding
- Black conductors (standard)
- Optional:
- Method1 K1 or K2
Certifications/Compliances
- UL 1277, Tray Cable (TC) (optional)CPE & LSZH only)
- UL 44, Thermoset Insulated Wires and Cables
- UL 1685 / FT4, Vertical Tray Flame Test rated
- IEEE 1202 / 383 (70,000 BTU / hr), Vertical Flame Test rated (optional)
- ICEA T-30-520 (70,000 BTU / hr), Vertical Flame Test rated
- XLPE (RHW-2 rated), 90°C wet / dry
- UV sunlight resistant SUN RES (all colours)
- Direct burial rated
- -40°C cold bend rated
- Rated for use in hazardous locations:
- Class I Zone 2 (Div 2)
- Class II Zone 22 (Div 2)
|
Part Number | Number of Conductors | Conductor Size (AWG/MCM) | Nominal Diameter Overall Cable (in/mm) | Cable Weight (lbs/1000ft)/ (kg/km) | Ampacity (30°C ambient) | Max. Pulling Tension (Pulling Eye) (lb/kg) | Min. Bend Radius (Pull) (in/mm) |
2K010U140200300 | 2 | 14 | 0.492 / 12.5 | 111 / 165 | 25 | 66 / 30 | 4.4 / 112 |
2K010U120200300 | 2 | 12 | 0.528 / 13.41 | 136 / 202 | 30 | 104 / 47 | 4.8 / 121 |
2K010U100200300 | 2 | 10 | 0.608 / 15.44 | 191 / 284 | 40 | 166 / 75 | 5.5 / 139 |
2K010U080200300 | 2 | 8 | 0.706 / 17.93 | 261 / 388 | 55 | 265 / 120 | 6.4 / 161 |
2K010U060200300 | 2 | 6 | 0.784 / 19.91 | 346 / 516 | 75 | 419 / 190 | 7.1 / 179 |
2K010U040200300 | 2 | 4 | 0.918 / 23.32 | 513 / 764 | 95 | 668 / 303 | 8.3 / 210 |
2K010U030200300 | 2 | 3 | 0.972 / 24.69 | 608 / 904 | 115 | 842 / 382 | 8.7 / 222 |
2K010U020200300 | 2 | 2 | 1.034 / 26.26 | 718 / 1069 | 130 | 1062 / 482 | 9.3 / 236 |
2K010U010240300 | 2 | 1 | 1.192 / 30.28 | 915 / 1362 | 145 | 1339 / 607 | 10.7 / 272 |
2K010U1/0240300 | 2 | 1/0 | 1.272 / 32.31 | 1100 / 1637 | 170 | 1690 / 766 | 11.4 / 291 |
2K010U2/0240300 | 2 | 2/0 | 1.358 / 34.49 | 1321 / 1966 | 195 | 2130 / 966 | 12.2 / 310 |
2K010U3/0240300 | 2 | 3/0 | 1.46 / 37.08 | 1594 / 2372 | 225 | 2671 / 1212 | 13.1 / 334 |
2K010U4/0240300 | 2 | 4/0 | 1.572 / 39.93 | 1932 / 2876 | 260 | 3386 / 1536 | 14.1 / 359 |
2K010U250260300 | 2 | 250 | 1.784 / 45.31 | 2366 / 3520 | 290 | 4000 / 1814 | 16.1 / 408 |
2K010U300260300 | 2 | 300 | 1.89 / 48.01 | 2754 / 4099 | 320 | 4800 / 2177 | 17 / 432 |
2K010U350260300 | 2 | 350 | 1.99 / 50.55 | 3138 / 4670 | 350 | 5600 / 2540 | 17.9 / 455 |
2K010U500260300 | 2 | 500 | 2.246 / 57.05 | 4259 / 6338 | 430 | 8000 / 3629 | 20.2 / 513 |
2K010U140300300 | 3 | 14 | 0.521 / 13.23 | 137 / 204 | 25 | 99 / 45 | 4.7 / 119 |
2K010U120300300 | 3 | 12 | 0.59 / 14.98 | 189 / 282 | 30 | 157 / 71 | 5.3 / 135 |
*Ampacity value based on National Electrical Code, Version 2020, Table 310.16. Values are corrected according to Table 310.15(C)(1) for number of Conductors. Per NEC 310.15(C)(1), the ampacity of 4/C cable shall be reduced by a factor of 0.8 when the neutral is considered a current-carrying conductor.
Part Number | Number of Conductors | Conductor Size (AWG/MCM) | Nominal Diameter Overall Cable (in/mm) | Cable Weight (lbs/1000ft)/ (kg/km) | Ampacity (30°C ambient) | Max. Pulling Tension (Pulling Eye) (lb/kg) | Min. Bend Radius (Pull) (in/mm) |
2K010U100300300 | 3 | 10 | 0.643 / 16.34 | 244 / 363 | 40 | 249 / 113 | 5.8 / 147 |
2K010U080300300 | 3 | 8 | 0.749 / 19.02 | 339 / 505 | 55 | 397 / 180 | 6.7 / 171 |
2K010U060300300 | 3 | 6 | 0.832 / 21.14 | 458 / 682 | 75 | 629 / 285 | 7.5 / 190 |
2K010U040300300 | 3 | 4 | 0.973 / 24.72 | 680 / 1012 | 95 | 1002 / 454 | 8.8 / 223 |
2K010U030300300 | 3 | 3 | 1.031 / 26.2 | 811 / 1207 | 115 | 1263 / 573 | 9.3 / 236 |
2K010U020300300 | 3 | 2 | 1.098 / 27.89 | 972 / 1446 | 130 | 1593 / 723 | 9.9 / 251 |
2K010U010340300 | 3 | 1 | 1.268 / 32.2 | 1235 / 1838 | 145 | 2009 / 911 | 11.4 / 290 |
2K010U1/0340300 | 3 | 1/0 | 1.354 / 34.39 | 1491 / 2219 | 170 | 2534 / 1150 | 12.2 / 310 |
2K010U2/0340300 | 3 | 2/0 | 1.446 / 36.74 | 1803 / 2684 | 195 | 3194 / 1449 | 13 / 331 |
2K010U3/0340300 | 3 | 3/0 | 1.556 / 39.52 | 2191 / 3261 | 225 | 4007 / 1818 | 14 / 356 |
2K010U4/0340300 | 3 | 4/0 | 1.676 / 42.58 | 2677 / 3984 | 260 | 5078 / 2304 | 15.1 / 383 |
2K010U250360300 | 3 | 250 | 1.9 / 48.25 | 3248 / 4833 | 290 | 6000 / 2722 | 17.1 / 434 |
2K010U300360300 | 3 | 300 | 2.014 / 51.15 | 3793 / 5645 | 320 | 7200 / 3266 | 18.1 / 460 |
2K010U350360300 | 3 | 350 | 2.121 / 53.88 | 4338 / 6456 | 350 | 8400 / 3810 | 19.1 / 485 |
2K010U500360300 | 3 | 500 | 2.396 / 60.87 | 5944 / 8846 | 430 | 12000 / 5443 | 21.6 / 548 |
2K010U750360300 | 3 | 750 | 2.906 / 73.81 | 8860 / 13185 | 535 | 18000 / 8165 | 26.2 / 664 |
2K010U140400300 | 4 | 14 | 0.601 / 15.27 | 188 / 280 | 20 | 132 / 60 | 5.4 / 137 |
2K010U120400300 | 4 | 12 | 0.645 / 16.37 | 235 / 349 | 24 | 209 / 95 | 5.8 / 147 |
2K010U100400300 | 4 | 10 | 0.705 / 17.9 | 306 / 456 | 32 | 332 / 151 | 6.3 / 161 |
2K010U080400300 | 4 | 8 | 0.823 / 20.9 | 427 / 636 | 44 | 529 / 240 | 7.4 / 188 |
2K010U060400300 | 4 | 6 | 0.956 / 24.28 | 617 / 917 | 60 | 839 / 380 | 8.6 / 219 |
2K010U040400300 | 4 | 4 | 1.069 / 27.16 | 869 / 1293 | 76 | 1336 / 606 | 9.6 / 244 |
2K010U030400300 | 4 | 3 | 1.134 / 28.81 | 1032 / 1535 | 92 | 1684 / 764 | 10.2 / 259 |
2K010U020400300 | 4 | 2 | 1.209 / 30.71 | 1246 / 1854 | 104 | 2124 / 964 | 10.9 / 276 |
2K010U010440300 | 4 | 1 | 1.399 / 35.54 | 1592 / 2369 | 116 | 2678 / 1215 | 12.6 / 320 |
2K010U1/0440300 | 4 | 1/0 | 1.496 / 37.99 | 1925 / 2864 | 136 | 3379 / 1533 | 13.5 / 342 |
2K010U2/0440300 | 4 | 2/0 | 1.6 / 40.63 | 2340 / 3483 | 156 | 4259 / 1932 | 14.4 / 366 |
2K010U3/0440300 | 4 | 3/0 | 1.782 / 45.27 | 2947 / 4385 | 180 | 5343 / 2423 | 16 / 407 |
2K010U4/0440300 | 4 | 4/0 | 1.917 / 48.7 | 3597 / 5352 | 208 | 6771 / 3071 | 17.3 / 438 |
2K010U250460300 | 4 | 250 | 2.1 / 53.35 | 4207 / 6261 | 232 | 8000 / 3629 | 18.9 / 480 |
2K010U300460300 | 4 | 300 | 2.228 / 56.6 | 4933 / 7342 | 256 | 9600 / 4355 | 20.1 / 509 |
2K010U350460300 | 4 | 350 | 2.349 / 59.66 | 5649 / 8407 | 280 | 11200 / 5080 | 21.1 / 537 |
2K010U500460300 | 4 | 500 | 2.657 / 67.49 | 7759 / 11547 | 344 | 16000 / 7258 | 23.9 / 607 |
*Ampacity value based on National Electrical Code, Version 2020, Table 310.16. Values are corrected according to Table 310.15(C)(1) for number of Conductors. Per NEC 310.15(C)(1), the ampacity of 4/C cable shall be reduced by a factor of 0.8 when the neutral is considered a current-carrying conductor.
|
|