CSA TYPE TECK 90 Armoured Power, Single-Conductor, 1000 V

Armoured power cable is used to supply power for lighting, drives, motors and pumps. Interlocked armour replaces the use of conduit for mechanical protection. Cable can be directly buried, installed in raceways, including cable tray in wet or dry environments. Cable is suitable for use in outdoor exposed applications and is rated for damp or dry locations in -40°C (-40°F) environments
CSA

Construction

VOLTAGE

1000 V
Optional: 600 V

PRODUCT CONSTRUCTION

Insulation:
XLPE (RW90 rated) rated: 90°C wet/dry

Bonding Conductor:
Concentric serving of solid bare copper wires applied over the insulation

Armour:
Aluminum Interlocked Armour (AIA) (standard)

Jacket:
FR LAG PVC (AG14 rated) outer black jacket rated: 90°C to -40°C

Available in:
Ribbed inner-jacketed core for vertical/mineshaft applications
Custom insulation/jacket colours
Aluminum conductors

Certifications

CERTIFICATION/COMPLIANCES

  • CSA C22.2 NO. 131, Type TECK 90 cable
  • CSA C22.2 NO. 174, Cables and cable glands for use in hazardous locations
  • CSA C22.2 NO. 38, Thermoset Insulated Wires & Cables (XLPE)
  • CSA C22.2 No. 2556/UL 2556 FT4, Vertical Tray Flame Test rated
  • IEEE 383/1202 (70,000 BTU/hr), Vertical Flame Test rated
  • XLPE (RW90 rated), 90°C wet/dry
  • UV sunlight resistant “SUN RES” (all colours)
  • Direct burial rated
  • -40°C cold bend/impact rated
  • HL rated for use in hazardous locations:
    • Zone 0 (Class 1, Division 1) (Intrinsically Safe circuits only)
    • Zone 1 (Class I, Division 1), Zone 2 (Class I, Division 2)
    • Zone 20 & 21 (Class II & III, Division 1), Zone 22
      (Class II & III, Division 2)

COLOUR CODING

  • Black conductor (standard)

Properties

  1. Stranded Bare (ASTM B8) Annealed Copper Conductor
  2. XLPE (RW90 Rated) Insulated Conductor
  3. Bonding Conductor, Copper Wire Served Helically
  4. FR LAG PVC Inner Protective Jacket
  5. Aluminum Interlocked Armour (AIA)
  6. FR LAG PVC Outer Protective Jacket

CSA Type TECK 90 Armoured Power, Single-Conductor, Construction

Part Number Number of Conductors Conductor Size Bonding Conductor Size Nominal Diameter Cable Weight Ampacity* Max. Pulling Tension (Pulling Eye) Min. Bend Radius (Pull)
AWG or kcmil AWG Over Inner Jacket
in. | mm
Over Armour
in. | mm
Overall Cable
in. | mm
lb|1000ft |
kg|km
30°C ambient lb | kg in. | mm
80210M040100700 1 4 6 0.523 | 13.3 0.763 | 19.3 0.855 | 21.7 442 | 658 140 334 | 151 15.4 | 391
80210M020100700 1 2 6 0.581 | 14.8 0.821 | 20.9 0.913 | 23.2 541 | 805 190 531 | 241 16.4 | 417
80210M010140700 1 1 4 0.716 | 18.2 0.956 | 24.3 1.048 | 26.6 721 | 1073 220 670 | 304 18.9 | 479
80210M1/0140700 1 1/0 4 0.756 | 19.2 0.996 | 25.3 1.088 | 27.6 807 | 1201 260 845 | 383 19.6 | 497
80210M2/0140700 1 2/0 4 0.799 | 20.3 1.039 | 26.4 1.131 | 28.7 956 | 1423 300 1065 | 483 20.4 | 517
80210M3/0140700 1 3/0 3 0.850 | 21.6 1.090 | 27.7 1.182 | 30.0 1116 | 1661 350 1336 | 606 21.3 | 540
80210M4/0140700 1 4/0 3 0.906 | 23.0 1.146 | 29.1 1.238 | 31.5 1279 | 1904 405 1693 | 768 22.3 | 566
80210M250160700 1 250 2 1.002 | 25.5 1.242 | 31.6 1.334 | 33.9 1518 | 2260 455 2000 | 907 24.0 | 610
80210M300160700 1 300 2 1.055 | 26.8 1.295 | 32.9 1.387 | 35.2 1701 | 2532 500 2400 | 1089 25.0 | 634
80210M350160700 1 350 1 1.105 | 28.1 1.345 | 34.2 1.437 | 36.5 1938 | 2885 570 2800 | 1270 25.9 | 657
80210M500160700 1 500 1|0 1.233 | 31.3 1.473 | 37.4 1.565 | 39.8 2542 | 3782 700 4000 | 1814 28.2 | 716
80210M750160700 1 750 2|0 1.412 | 35.9 1.652 | 42.0 1.760 | 44.7 3541 | 5270 885 6000 | 2722 31.7 | 805
80210MA00160700 1 1000 2|0 1.561 | 39.7 1.866 | 47.4 1.974 | 50.1 4474 | 6658 1055 8000 | 3629 35.5 | 903

*Ampacity value based on Canadian Electrical Code, Part 1 (2021 25th Edition), Table 1.
The size of the concentrically applied bonding conductor shall be determined from the sum of the cross-sectional areas of the individual wires.

Markets / Applications

  • Renewables – Wind, Solar, Geo Thermal
  • Shipboard
  • Mining
  • Utility
  • Oil and Gas
  • Water/Waste Water Treatment
  • Commercial Construction Projects
  • Communication Power & Control
  • Power Distribution
  • Industrial Construction/Automation
  • Civil Construction Projects
  • Petrochem/Pulp & Paper

VOLTAGE

1000 V
Optional: 600 V

PRODUCT CONSTRUCTION

Insulation:
XLPE (RW90 rated) rated: 90°C wet/dry

Bonding Conductor:
Concentric serving of solid bare copper wires applied over the insulation

Armour:
Aluminum Interlocked Armour (AIA) (standard)

Jacket:
FR LAG PVC (AG14 rated) outer black jacket rated: 90°C to -40°C

Available in:
Ribbed inner-jacketed core for vertical/mineshaft applications
Custom insulation/jacket colours
Aluminum conductors

CERTIFICATION/COMPLIANCES

  • CSA C22.2 NO. 131, Type TECK 90 cable
  • CSA C22.2 NO. 174, Cables and cable glands for use in hazardous locations
  • CSA C22.2 NO. 38, Thermoset Insulated Wires & Cables (XLPE)
  • CSA C22.2 No. 2556/UL 2556 FT4, Vertical Tray Flame Test rated
  • IEEE 383/1202 (70,000 BTU/hr), Vertical Flame Test rated
  • XLPE (RW90 rated), 90°C wet/dry
  • UV sunlight resistant “SUN RES” (all colours)
  • Direct burial rated
  • -40°C cold bend/impact rated
  • HL rated for use in hazardous locations:
    • Zone 0 (Class 1, Division 1) (Intrinsically Safe circuits only)
    • Zone 1 (Class I, Division 1), Zone 2 (Class I, Division 2)
    • Zone 20 & 21 (Class II & III, Division 1), Zone 22
      (Class II & III, Division 2)

COLOUR CODING

  • Black conductor (standard)
  1. Stranded Bare (ASTM B8) Annealed Copper Conductor
  2. XLPE (RW90 Rated) Insulated Conductor
  3. Bonding Conductor, Copper Wire Served Helically
  4. FR LAG PVC Inner Protective Jacket
  5. Aluminum Interlocked Armour (AIA)
  6. FR LAG PVC Outer Protective Jacket

CSA Type TECK 90 Armoured Power, Single-Conductor, Construction

Part Number Number of Conductors Conductor Size Bonding Conductor Size Nominal Diameter Cable Weight Ampacity* Max. Pulling Tension (Pulling Eye) Min. Bend Radius (Pull)
AWG or kcmil AWG Over Inner Jacket
in. | mm
Over Armour
in. | mm
Overall Cable
in. | mm
lb|1000ft |
kg|km
30°C ambient lb | kg in. | mm
80210M040100700 1 4 6 0.523 | 13.3 0.763 | 19.3 0.855 | 21.7 442 | 658 140 334 | 151 15.4 | 391
80210M020100700 1 2 6 0.581 | 14.8 0.821 | 20.9 0.913 | 23.2 541 | 805 190 531 | 241 16.4 | 417
80210M010140700 1 1 4 0.716 | 18.2 0.956 | 24.3 1.048 | 26.6 721 | 1073 220 670 | 304 18.9 | 479
80210M1/0140700 1 1/0 4 0.756 | 19.2 0.996 | 25.3 1.088 | 27.6 807 | 1201 260 845 | 383 19.6 | 497
80210M2/0140700 1 2/0 4 0.799 | 20.3 1.039 | 26.4 1.131 | 28.7 956 | 1423 300 1065 | 483 20.4 | 517
80210M3/0140700 1 3/0 3 0.850 | 21.6 1.090 | 27.7 1.182 | 30.0 1116 | 1661 350 1336 | 606 21.3 | 540
80210M4/0140700 1 4/0 3 0.906 | 23.0 1.146 | 29.1 1.238 | 31.5 1279 | 1904 405 1693 | 768 22.3 | 566
80210M250160700 1 250 2 1.002 | 25.5 1.242 | 31.6 1.334 | 33.9 1518 | 2260 455 2000 | 907 24.0 | 610
80210M300160700 1 300 2 1.055 | 26.8 1.295 | 32.9 1.387 | 35.2 1701 | 2532 500 2400 | 1089 25.0 | 634
80210M350160700 1 350 1 1.105 | 28.1 1.345 | 34.2 1.437 | 36.5 1938 | 2885 570 2800 | 1270 25.9 | 657
80210M500160700 1 500 1|0 1.233 | 31.3 1.473 | 37.4 1.565 | 39.8 2542 | 3782 700 4000 | 1814 28.2 | 716
80210M750160700 1 750 2|0 1.412 | 35.9 1.652 | 42.0 1.760 | 44.7 3541 | 5270 885 6000 | 2722 31.7 | 805
80210MA00160700 1 1000 2|0 1.561 | 39.7 1.866 | 47.4 1.974 | 50.1 4474 | 6658 1055 8000 | 3629 35.5 | 903

*Ampacity value based on Canadian Electrical Code, Part 1 (2021 25th Edition), Table 1.
The size of the concentrically applied bonding conductor shall be determined from the sum of the cross-sectional areas of the individual wires.