CSA TYPE TECK 90 Armoured Power, Multi-Conductor, Shielded, 5000 V
Construction
Voltage
5000 V
Product Construction
Conductor Shield:
Extruded, concentric, thermoset semiconducting material
Insulation:
XLPE (RW90 rated) rated: 90°C wet/dry
Insulation Shield:
Extruded, concentric, thermoset semiconducting layer + metallic shield
Armour:
Aluminum Interlocked Armour (AIA) (standard)
Steel Interlocked Armour (SIA) (optional)
Jacket:
FR LAG PVC (AG14 rated) inner black jacket rated: 90°C to -40°C
FR LAG PVC (AG14 rated) outer orange jacket rated: 90°C to -40°C
Available in:
Variable Frequency Drive (VFD)
Ribbed inner-jacketed core for vertical/mineshaft applications
Custom insulation/jacket colours
Composite constructions
Aluminum conductors
Certifications
Certifications/Compliances
- CSA C22.2 No. 131, Type TECK 90 cable
- CSA C22.2 No. 174, Cables and cable glands for use in hazardous locations
- CSA C22.2 No. 38, Thermoset-insulated wires and cables
- CSA C22.2 No. 2556/UL 2556 FT4, Vertical Tray Flame Test rated
- IEEE 383/1202 (70,000 BTU/hr), Vertical Flame Test rated
- XLPE (RW90 rated), 90°C wet/dry
- UV sunlight resistant “SUN RES” (all colours)
- Direct burial rated
- -40°C cold bend/impact rated
- HL rated for use in hazardous locations:
- Zone 0 (Class 1, Division 1) (Intrinsically Safe circuits only)
- Zone 1 (Class I, Division 1), Zone 2 (Class I, Division 2)
- Zone 20 & 21 (Class II & III, Division 1), Zone 22 (Class II & III, Division 2)
Colour Coding
- 2C – Black & white
- 3C – Black, red & blue
- 4C – Black, red, blue & white
- 5C and greater – Black, number-coded with white ink
Properties
- Stranded Bare (ASTM B8) Annealed Copper Conductors
- Semiconducting Conductor Shield
- Bonding Conductor
- XLPE (RW90 Rated) Insulated Conductors
- Semiconducting Insulation Shield
- Copper Tape Shield
- Polyester Separator Tape
- FR LAG PVC Inner Protective Jacket
- Aluminum Interlocked Armour (AIA)
- FR LAG PVC Outer Protective Jacket
| Part Number | Number of Conductors | Conductor Size | Bonding Conductor Size | Nominal Diameter | Cable Weight | Ampacity* | Max. Pulling Tension (Pulling Eye) | Min. Bend Radius (Pull) | ||
| AWG or kcmil | AWG | Over Inner Jacket in. | mm |
Over Armour in. | mm |
Overall Cable in. | mm |
lb/1000ft | kg/km |
30°C ambient | lb | kg | in. | mm | ||
| 8S210M060305700 | 3 | 6 | 8 | 1.159 | 29.4 | 1.399 | 35.5 | 1.491 | 37.9 | 1093 | 1626 | 75 | 630 | 286 | 26.8 | 682 |
| 8S210M040305700 | 3 | 4 | 8 | 1.260 | 32.0 | 1.500 | 38.1 | 1.592 | 40.4 | 1323 | 1970 | 95 | 1002 | 454 | 28.7 | 728 |
| 8S210M030305700 | 3 | 3 | 8 | 1.318 | 33.5 | 1.558 | 39.6 | 1.666 | 42.3 | 1537 | 2288 | 115 | 1263 | 573 | 30.0 | 762 |
| 8S210M020305700 | 3 | 2 | 8 | 1.385 | 35.2 | 1.625 | 41.3 | 1.733 | 44.0 | 1710 | 2545 | 130 | 1593 | 722 | 31.2 | 792 |
| 8S210M010345700 | 3 | 1 | 6 | 1.469 | 37.3 | 1.709 | 43.4 | 1.817 | 46.2 | 1961 | 2918 | 145 | 2009 | 911 | 32.7 | 831 |
| 8S210M1/0345700 | 3 | 1/0 | 6 | 1.555 | 39.5 | 1.860 | 47.2 | 1.968 | 50.0 | 2316 | 3447 | 170 | 2534 | 1150 | 35.4 | 900 |
| 8S210M2/0345700 | 3 | 2/0 | 6 | 1.476 | 37.5 | 1.953 | 49.6 | 2.061 | 52.3 | 2657 | 3954 | 195 | 3194 | 1449 | 37.1 | 942 |
| 8S210M3/0345700 | 3 | 3/0 | 4 | 1.818 | 46.2 | 2.123 | 53.9 | 2.231 | 56.7 | 3250 | 4837 | 225 | 4027 | 1827 | 40.2 | 1020 |
| 8S210M4/0345700 | 3 | 4/0 | 4 | 1.938 | 49.2 | 2.243 | 57.0 | 2.351 | 59.7 | 3793 | 5644 | 260 | 5078 | 2304 | 42.3 | 1075 |
| 8S210M250365700 | 3 | 250 | 4 | 2.059 | 52.3 | 2.364 | 60.0 | 2.496 | 63.4 | 4368 | 6500 | 290 | 6000 | 2722 | 44.9 | 1141 |
| 8S210M300365700 | 3 | 300 | 4 | 2.173 | 55.2 | 2.478 | 62.9 | 2.610 | 66.3 | 4975 | 7404 | 320 | 7200 | 3266 | 47.0 | 1193 |
| 8S210M350365700 | 3 | 350 | 3 | 2.281 | 57.9 | 2.586 | 65.7 | 2.718 | 69.0 | 5573 | 8294 | 350 | 8400 | 3810 | 48.9 | 1243 |
| 8S210M500365700 | 3 | 500 | 3 | 2.557 | 64.9 | 2.862 | 72.7 | 2.994 | 76.0 | 7267 | 10814 | 430 | 12000 | 5443 | 53.9 | 1369 |
| 8S210M750365700 | 3 | 750 | 2 | 3.020 | 76.7 | 3.325 | 84.5 | 3.471 | 88.2 | 10364 | 15424 | 535 | 18000 | 8165 | 62.5 | 1587 |
*Ampacity value based on Canadian Electrical Code, Part 1 (2021 25th Edition), Table 2. Values are corrected for number of insulated conductors as applicable according to Table 5C.
Markets / Applications
- Generation – Renewables – Wind
- Transit
- Water/Waste Water Treatment
- Generation – Traditional Power
- Generation
- Communication Power & Control
- Generation – Nuclear
- Power Distribution
- Industrial Construction/Automation
- Civil Construction Projects
- Power Distribution – LV
- Industrial
- Generation – Renewables
- Petrochem/Pulp & Paper
- Power Distribution – MV
- Utility
- Commercial Construction Projects
- OIl & Gas
- Generation – Renewables – Geo Thermal
- Generation – Renewables – Solar
- Mining
Voltage
5000 V
Product Construction
Conductor Shield:
Extruded, concentric, thermoset semiconducting material
Insulation:
XLPE (RW90 rated) rated: 90°C wet/dry
Insulation Shield:
Extruded, concentric, thermoset semiconducting layer + metallic shield
Armour:
Aluminum Interlocked Armour (AIA) (standard)
Steel Interlocked Armour (SIA) (optional)
Jacket:
FR LAG PVC (AG14 rated) inner black jacket rated: 90°C to -40°C
FR LAG PVC (AG14 rated) outer orange jacket rated: 90°C to -40°C
Available in:
Variable Frequency Drive (VFD)
Ribbed inner-jacketed core for vertical/mineshaft applications
Custom insulation/jacket colours
Composite constructions
Aluminum conductors
Certifications/Compliances
- CSA C22.2 No. 131, Type TECK 90 cable
- CSA C22.2 No. 174, Cables and cable glands for use in hazardous locations
- CSA C22.2 No. 38, Thermoset-insulated wires and cables
- CSA C22.2 No. 2556/UL 2556 FT4, Vertical Tray Flame Test rated
- IEEE 383/1202 (70,000 BTU/hr), Vertical Flame Test rated
- XLPE (RW90 rated), 90°C wet/dry
- UV sunlight resistant “SUN RES” (all colours)
- Direct burial rated
- -40°C cold bend/impact rated
- HL rated for use in hazardous locations:
- Zone 0 (Class 1, Division 1) (Intrinsically Safe circuits only)
- Zone 1 (Class I, Division 1), Zone 2 (Class I, Division 2)
- Zone 20 & 21 (Class II & III, Division 1), Zone 22 (Class II & III, Division 2)
Colour Coding
- 2C – Black & white
- 3C – Black, red & blue
- 4C – Black, red, blue & white
- 5C and greater – Black, number-coded with white ink
- Stranded Bare (ASTM B8) Annealed Copper Conductors
- Semiconducting Conductor Shield
- Bonding Conductor
- XLPE (RW90 Rated) Insulated Conductors
- Semiconducting Insulation Shield
- Copper Tape Shield
- Polyester Separator Tape
- FR LAG PVC Inner Protective Jacket
- Aluminum Interlocked Armour (AIA)
- FR LAG PVC Outer Protective Jacket
| Part Number | Number of Conductors | Conductor Size | Bonding Conductor Size | Nominal Diameter | Cable Weight | Ampacity* | Max. Pulling Tension (Pulling Eye) | Min. Bend Radius (Pull) | ||
| AWG or kcmil | AWG | Over Inner Jacket in. | mm |
Over Armour in. | mm |
Overall Cable in. | mm |
lb/1000ft | kg/km |
30°C ambient | lb | kg | in. | mm | ||
| 8S210M060305700 | 3 | 6 | 8 | 1.159 | 29.4 | 1.399 | 35.5 | 1.491 | 37.9 | 1093 | 1626 | 75 | 630 | 286 | 26.8 | 682 |
| 8S210M040305700 | 3 | 4 | 8 | 1.260 | 32.0 | 1.500 | 38.1 | 1.592 | 40.4 | 1323 | 1970 | 95 | 1002 | 454 | 28.7 | 728 |
| 8S210M030305700 | 3 | 3 | 8 | 1.318 | 33.5 | 1.558 | 39.6 | 1.666 | 42.3 | 1537 | 2288 | 115 | 1263 | 573 | 30.0 | 762 |
| 8S210M020305700 | 3 | 2 | 8 | 1.385 | 35.2 | 1.625 | 41.3 | 1.733 | 44.0 | 1710 | 2545 | 130 | 1593 | 722 | 31.2 | 792 |
| 8S210M010345700 | 3 | 1 | 6 | 1.469 | 37.3 | 1.709 | 43.4 | 1.817 | 46.2 | 1961 | 2918 | 145 | 2009 | 911 | 32.7 | 831 |
| 8S210M1/0345700 | 3 | 1/0 | 6 | 1.555 | 39.5 | 1.860 | 47.2 | 1.968 | 50.0 | 2316 | 3447 | 170 | 2534 | 1150 | 35.4 | 900 |
| 8S210M2/0345700 | 3 | 2/0 | 6 | 1.476 | 37.5 | 1.953 | 49.6 | 2.061 | 52.3 | 2657 | 3954 | 195 | 3194 | 1449 | 37.1 | 942 |
| 8S210M3/0345700 | 3 | 3/0 | 4 | 1.818 | 46.2 | 2.123 | 53.9 | 2.231 | 56.7 | 3250 | 4837 | 225 | 4027 | 1827 | 40.2 | 1020 |
| 8S210M4/0345700 | 3 | 4/0 | 4 | 1.938 | 49.2 | 2.243 | 57.0 | 2.351 | 59.7 | 3793 | 5644 | 260 | 5078 | 2304 | 42.3 | 1075 |
| 8S210M250365700 | 3 | 250 | 4 | 2.059 | 52.3 | 2.364 | 60.0 | 2.496 | 63.4 | 4368 | 6500 | 290 | 6000 | 2722 | 44.9 | 1141 |
| 8S210M300365700 | 3 | 300 | 4 | 2.173 | 55.2 | 2.478 | 62.9 | 2.610 | 66.3 | 4975 | 7404 | 320 | 7200 | 3266 | 47.0 | 1193 |
| 8S210M350365700 | 3 | 350 | 3 | 2.281 | 57.9 | 2.586 | 65.7 | 2.718 | 69.0 | 5573 | 8294 | 350 | 8400 | 3810 | 48.9 | 1243 |
| 8S210M500365700 | 3 | 500 | 3 | 2.557 | 64.9 | 2.862 | 72.7 | 2.994 | 76.0 | 7267 | 10814 | 430 | 12000 | 5443 | 53.9 | 1369 |
| 8S210M750365700 | 3 | 750 | 2 | 3.020 | 76.7 | 3.325 | 84.5 | 3.471 | 88.2 | 10364 | 15424 | 535 | 18000 | 8165 | 62.5 | 1587 |
*Ampacity value based on Canadian Electrical Code, Part 1 (2021 25th Edition), Table 2. Values are corrected for number of insulated conductors as applicable according to Table 5C.
- Generation – Renewables – Wind
- Transit
- Water/Waste Water Treatment
- Generation – Traditional Power
- Generation
- Communication Power & Control
- Generation – Nuclear
- Power Distribution
- Industrial Construction/Automation
- Civil Construction Projects
- Power Distribution – LV
- Industrial
- Generation – Renewables
- Petrochem/Pulp & Paper
- Power Distribution – MV
- Utility
- Commercial Construction Projects
- OIl & Gas
- Generation – Renewables – Geo Thermal
- Generation – Renewables – Solar
- Mining