Teck 90 cables are suitable for use in ventilated, non-ventilated and ladder type cable trays, direct earth burial or
raceways, and for exposed or concealed wiring in wet, damp or dry locations in -40°C (-40°F) environments.
| Conductors: |
7 strand concentric, Class B bare or tinned copper wire, #14 to 2 AWG (2.08 to 33.08 mm²) for 600 V and 1000
V cable. #6 to 2 AWG (13.06 to 33.08 mm²) are compressed strand copper wire |
| Primary Insulation: |
XLPE compound - rated as 105°C (221°F) dry, 90°C (194°F) wet, and -40°C (-40°F) for Type RW90-40 insulation |
| Conductor Identification: |
2 conductor cables are colour Coded: Black and White |
| 3 conductor cables are colour coded: Black, Red and Blue |
| 4 conductor cables are colour coded: Black, Red, Blue and White |
| 5 or more conductor cables are black and alpha numeric coded |
| Bonding Conductor: |
Bare copper bonding conductor sized in accordance with Table 16 of the Canadian Electrical Code |
| Jacket: |
90°C (194°F) to -40°C (-40°F) Fire Retardant Low Acid Gas PVC |
| The standard inner jacket under the armour is black. Other colours are available upon request |
| Armouring: |
CSA certified interlocked aluminum or interlocked galvanized steel armour is suitable for use in Hazardous Locations.
These cables are marked HL in accordance with CSA C22.2 No. 174 |
| Armour Outer Covering: |
90°C (194°F) to -40°C (-40°F) Fire Retardant (FR) Low Acid Gas (LAG) PVC |
Teck 90 cable standard colour is black. Other colours are available upon request |