ShawFlex Home
Home About ShawFlex Product Information Literature News Resources Contact Us
Cable Photo
Product Information Power and Control Tray Cable Cable Equipment

These cables are suitable for use in raceways, ventilated, non-ventilated and ladder type cable trays, direct earth burial, and for exposed or concealed wiring in wet, damp or dry locations in -40°C (-40°F) environments.

Design Standards

Conductors: 7 strand concentric, Class B bare or tinned copper wire. Available in #20 to 14 AWG (0.519 to 2.08 mm²) for 300 V, #18 to 2 AWG (0.823 to 33.08 mm²) for 600 V and #14 to 2 AWG (2.08 to 33.08 mm²) for 1000 V
Primary Insulation: PVC compound - rated as 75°C (167°F) dry, 75°C (167°F) wet and -40°C (-40°F) for Type TW75-40 insulation
FR XLPE compound - rated as 105°C (221°F) dry, 90°C (194°F) wet and -40°C (-40°F) for Type RW90-40 insulation
Conductor Identification: 2 conductor cables are colour coded: Black and White
3 conductor cables are colour coded: Black, Red and Blue
4 conductor cables are colour coded: Black, Red, Blue and White
5 or more conductors cables are black and alpha numeric coded
Bonding Conductor: Bare copper bonding conductor sized in accordance with Table 16 of the Canadian Electrical Code

Standard Performance Features

  • Cables meet cold impact/bend test at -40°C (-40°F), however we do not recommend that cables be installed if the cable temperature is below -10°C (-14°F)
  • Cables are CSA Certified for use in Hazardous Locations
  • Sunlight Resistant
  • Flame Test rated FT4

CSA Certifications

  • CSA C22.2 No. 239, Control and Instrumentation Cables
  • CSA C22.2 No. 38, Thermoset Insulated Conductors
  • CSA C22.2 No. 230, Tray Cables