Power and Control Tray Cable

These cables are suitable for use in raceways, ventilated, non-ventilated and ladder type cable trays, direct earth burial, and for exposed or concealed wiring in wet, damp or dry locations in -40°C (-40°F) environments.

Design Standards

Conductors:
7 strand concentric, Class B bare or tinned copper wire. Available in #20 to 14 AWG (0.519 to 2.08 mm²) for 300 V, #18 to 2 AWG (0.823 to 33.08 mm²) for 600 V and #14 to 2 AWG (2.08 to 33.08 mm²) for 1000 V
Primary Insulation:
PVC compound - rated as 75°C (167°F) dry, 75°C (167°F) wet and -40°C (-40°F) for Type TW75-40 insulationv
FR XLPE compound - rated as 105°C (221°F) dry, 90°C (194°F) wet and -40°C (-40°F) for Type RW90-40 insulation
Conductor Identification:
2 conductor cables are colour coded: Black and White
3 conductor cables are colour coded: Black, Red and Blue
4 conductor cables are colour coded: Black, Red, Blue and White
5 or more conductors cables are black and alpha numeric coded
Bonding Conductor:
Bare copper bonding conductor sized in accordance with Table 16 of the Canadian Electrical Code

Standard Performance Features

CSA Certifications