Page 6 - ShawFlex.com | UL Catalogue
P. 6


UL PLTC


V.2 | 6



TC
INSTRUMENTATION | PAIRS & TRIADS (300V) 
PAGE 1 OF 2 



Tray Instrumentation cables can be used to minimize noise and signal interference by 

preventing crosstalk between pairs and triads. This cable can also be used to carry analogue 
or digital signals. Tray Instrumentation cables can be installed in raceways, direct burial 
applications and in outdoor exposed industrial applications.


Voltage
Certifications/Compliances
300V
• UL 13, Power Limited Tray Cable (PLTC)
5

Product Construction
• UL 2250, Instrumentation Tray Cable (ITC) 1 2
3 4
6
• UL 83, Thermoplastic Insulated Wires and
• Insulation: Cables
- FR PVC
• UL 1685 / FT4, Vertical Tray Flame Test rated 

rated: 60°C wet/105°C dry • IEEE 1202/383 (70,000 BTU/hr), Vertical
- XLPE rated (optional)
Flame Test rated (optional)
- VW-1 rated (optional)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
1. Stranded Bare Copper Conductors (Tinned 
• Shielding (foil-free edge): Test rated
Available)
2. FR PVC Insulated Conductors
- ISOS (standard)
• UV sunlight resistant “SUN RES” (all colours) 3. Individual Shield & Overall Shielded Pairs/
- OS (optional)
• -40°C cold bend rated
• Armor:
• Rated for use in hazardous locations:
Triads with Tinned Copper Drain Wire
4. Polyester Separator Tape
- Zetabon (optional)
- Class I Zone 2 (Div 2)
5. Overall Aluminum/Mylar Shield with Tinned
• Jacket:
- Class II Zone 22 (Div 2)
-
FR PVC outer black jacket (standard) Copper Drain Wire
rated: 90°C to -40°C
6. FR PVC Protective Jacket
Colour Coding
- Thermoset CPE (optional) 
• Pairs - Black, & white, with black printing on - Thermoplastic CPE (optional) 
white (standard)
-
Thermoplastic LSZH (optional)
• Triads - Black, white & red, with black printing • Available in:

on white (standard)
- Custom insulation/jacket colors 
- Composite constructions
-
TC-ER with CPE jackets


NominalDiameterOverall 
Conductor Size CableWeight(lbs/1000ft)/ Max. Pulling Tension Min. Bend Radius (Pull)
Part Number Number of Pairs Cable 
(AWG/MCM) (kg/km) (Pulling Eye) (lb/kg) (in/mm) (in/mm)

23021U160100700 1 16 0.267 / 6.78 43 / 64 41 / 19 4.8 / 122

23022U160200700 2 16 0.426 / 10.81 104 / 155 82 / 37 7.7 / 195

23022U160400700 4 16 0.492 / 12.5 152 / 226 165 / 75 8.9 / 225
23022U160600700 6 16 0.586 / 14.88 216 / 321 247 / 112 10.5 / 268

23022U160800700 8 16 0.654 / 16.62 283 / 421 330 / 150 11.8 / 299

23022U161200700 12 16 0.791 / 20.09 401 / 597 494 / 224 14.2 / 362
23022U161600700 16 16 0.88 / 22.36 508 / 755 659 / 299 15.8 / 402

23022U162400700 24 16 1.111 / 28.21 761 / 1132 989 / 449 20 / 508

23022U163600700 36 16 1.276 / 32.4 1076 / 1601 1483 / 673 23 / 583
23021U180100700 1 18 0.243 / 6.17 34 / 51 26 / 12 4.4 / 111

23022U180200700 2 18 0.366 / 9.3 74 / 110 52 / 24 6.6 / 167
23022U180400700 4 18 0.444 / 11.27 118 / 175 104 / 47 8 / 203

23022U180600700 6 18 0.525 / 13.35 166 / 246 156 / 71 9.5 / 240

23022U180800700 8 18 0.568 / 14.42 204 / 303 208 / 94 10.2 / 260
23022U181200700 12 18 0.707 / 17.95 299 / 446 312 / 142 12.7 / 323

23022U181800700 18 18 0.827 / 21 420 / 625 468 / 212 14.9 / 378

23022U182400700 24 18 0.987 / 25.08 562 / 836 624 / 283 17.8 / 451
23022U183600700 36 18 1.131 / 28.73 791 / 1178 936 / 425 20.4 / 517

23021U200100700 1 20 0.211 / 5.36 26 / 38 16 / 7 3.8 / 96

23022U200200700 2 20 0.313 / 7.96 58 / 86 32 / 15 5.6 / 143
23022U200400700 4 20 0.36 / 9.14 82 / 121 64 / 29 6.5 / 164