Page 47 - ShawFlex.com | UL Catalogue
P. 47


UL EPR RHW-2


V.2 | 47




EPR | SINGLE CONDUCTOR (600V) 
PAGE 1 OF 1



For use in open wiring and raceways (with the exception of cable troughs and ventilated 

flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Maximum 
conductor temperature 90°C.



Voltage
Certifications/Compliances
600V
• UL 44, Thermoset Insulated Wires and Cables 

• IEEE 1202/383 (70,000 BTU/hr), Vertical
12
Product Construction
Flame Test rated (1/0 & larger) 
• Insulation:
• CT Use (1/0 and larger)
1. Strand Bare (ASTM B8) Annealed Copper 
- EPR (RHW-2 rated) (standard)
Colour Coding
Conductors
rated: 90°C wet/dry 2.
EPR (RHW-2 Rated) Insulated Conductor
• Available in:
• Black conductor (standard)
- All colours







Part Number
Number of Conductor Size InsulationThickness CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull) 
Conductors
(AWG/MCM)
(in/mm)
(kg/km)
(30°C ambient)
(Pulling Eye) (lb/kg)
(in/mm)
1Q010U14010BN00
23 / 34
33 / 15
1
14
0.045 / 1.14
35
1.5 / 37

1Q010U12010BN00
1.6 / 41
1
12
0.045 / 1.14
32 / 47
40
52 / 24

1.9 / 47
1Q010U10010BN00
1
10
0.045 / 1.14
46 / 68
55
83 / 38

1Q010U08010BN00
2.4 / 61
1
8
0.060 / 1.52
76 / 113
80
132 / 60
2.7 / 69
1Q010U06010BN00
1
6
0.060 / 1.52
111 / 165
105
210 / 95

1Q010U04010BN00
3.1 / 80
1
4
0.060 / 1.52
165 / 246
140
334 / 151

3.7 / 93
1Q010U02010BN00
1
2
0.060 / 1.52
250 / 372
190
531 / 241
1Q010U01014BN00
4.4 / 111
1
1
0.080 / 2.03
325 / 483
220
670 / 304

4.7 / 120
1Q010U1/014BN00
1
1/0
0.080 / 2.03
400 / 595
260
845 / 383

1Q010U2/014BN00
5.1 / 130
1
2/0
0.080 / 2.03
493 / 734
300
1065 / 483

5.6 / 142
1Q010U3/014BN00
1
3/0
0.080 / 2.03
611 / 909
350
1336 / 606
1Q010U4/014BN00 6.1 / 155 1
4/0
0.080 / 2.03
757 / 1126
405
1693 / 768

1Q010U25016BN00
6.8 / 172
1
250
0.095 / 2.41
890 / 1325
455
2000 / 907

1Q010U35016BN00
1
350
0.095 / 2.41
1218 / 1812
570
2800 / 1270
7.7 / 195
1Q010U50016BN00
1
500
0.095 / 2.41
1704 / 2536
700
4000 / 1814
8.8 / 225

1Q010U75016BN00
1
750
0.110 / 2.79
2541 / 3782
885
6000 / 2722
10.7 / 272


*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(17). Values are corrected according to Table 310.15(B)(17) for number of Conductors.
























1 800 668 4842 shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   44   45   46   47   48