Page 45 - ShawFlex.com | UL Catalogue
P. 45


UL HD-XHHW-2


V.2 | 45




HEAVY DUTY XHHW-2 | SINGLE CONDUCTOR (600V) 
PAGE 1 OF 1



Heavy Duty provides an extra level of reliability and is suitable for use in ventilated, non- 

ventilated and ladder type cable trays, direct burial and raceways. Applicable for use in 
Utilities, Industrial and Commercial applications.



Voltage
Certifications/Compliances
123
600V
• UL 44, Thermoset Insulated Wires and Cables 
Optional: 2000V
• UL 1685/ FT4, Vertical Tray Flame Test rated
• IEEE 1202/383 (70,000 BTU/hr), Vertical

Product Construction
Flame Test rated
1. High Strand Bare Copper Conductors (Tinned 
• Insulation:
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
Available)
- EPR (XHHW-2 rated)
Test rated
2. Ethylene Propylene Rubber (EPR) (XHHW-2 
• XLPE (XHHW-2 rated), 90°C wet/dry
Rated) Insulated Conductor
rated: 90°C wet/dry 
• Jacket:
• UV sunlight resistant “SUN RES” (all colours) 3. Thermoset CPE Protective Jacket
- Thermoplastic CPE black outer jacket (standard) • Direct burial rated
rated: 90°C
• -40°C cold bend rated
• Rated for use in hazardous locations:
- Thermoset CPE (optional) 
• Available in:
- Class I Zone 2 (Div 2)
- Custom insulation/jacket colours
- Class II Zone 20, 21 (Div 1)
-
Class II Zone 22 (Div 2)

Colour Coding

• Black conductor (standard)


Nominal Diameter 
Conductor Size CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull)
Part Number NumberofConductors Overall Cable 
(AWG/MCM) (kg/km) (30°C ambient) (Pulling Eye) (lb/kg) (in/mm) 
(in/mm)
4M010U140100400 1 14 0.175 / 4.45 25 / 37 25 33 / 15 1.6 / 40

4M010U120100400 1 12 0.193 / 4.9 34 / 51 30 52 / 24 1.7 / 44

4M010U100100400 1 10 0.218 / 5.54 48 / 72 40 83 / 38 2 / 50
4M010U080100400 1 8 0.307 / 7.8 87 / 129 55 132 / 60 2.8 / 70

4M010U060100400 1 6 0.344 / 8.74 123 / 183 75 210 / 95 3.1 / 79

4M010U040100400 1 4 0.391 / 9.93 179 / 267 95 334 / 151 3.5 / 89

4M010U030100400 1 3 0.418 / 10.62 218 / 324 115 421 / 191 3.8 / 96
4M010U020100400 1 2 0.449 / 11.4 266 / 396 130 531 / 241 4 / 103

4M010U010140400 1 1 0.538 / 13.67 349 / 519 145 670 / 304 4.8 / 123

4M010U1/0140400 1 1/0 0.578 / 14.68 426 / 634 170 845 / 383 5.2 / 132

4M010U2/0140400 1 2/0 0.621 / 15.77 521 / 776 195 1065 / 483 5.6 / 142
4M010U3/0140400 1 3/0 0.672 / 17.07 641 / 954 225 1336 / 606 6 / 154

4M010U4/0140400 1 4/0 0.728 / 18.49 790 / 1175 260 1693 / 768 6.6 / 166

4M010U250160400 1 250 0.834 / 21.18 962 / 1432 290 2000 / 907 7.5 / 191
4M010U300160400 1 300 0.887 / 22.53 1132 / 1685 320 2400 / 1089 8 / 203

4M010U350160400 1 350 0.937 / 23.8 1302 / 1938 350 2800 / 1270 8.4 / 214

4M010U500160400 1 500 1.065 / 27.05 1805 / 2686 430 4000 / 1814 9.6 / 243

4M010U750160400 1 750 1.274 / 32.36 2669 / 3972 535 6000 / 2722 11.5 / 291

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(17).












1 800 668 4842
shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   43   44   45   46   47