Page 43 - ShawFlex.com | UL Catalogue
P. 43


UL FR-EPR/CPE


V.2 | 43




CONTROL | MULTI-CONDUCTOR (600V) 
PAGE 1 OF 2



For use where flame retardance, oil and moisture/chemical resistance are critical. FR EPR 

cables can be installed in cable tray, free air, in raceways or in direct burial applications




Voltage
Certifications/Compliances
600V
• UL 1277, Tray Cable (TC-ER)

Optional: 2000V
• UL 44, Thermoset Insulated Wires and Cables 12345
• FT4,UL1685/T4,VerticalTrayFlameTestrated 
Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
Flame Test rated
• Insulation:
- FR EPR (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
1. Bare Copper Conductors (Tinned Available) 
rated: 90°C wet/dry
Test rated
2. FR Ethylene Propylene Rubber (EPR) Insulated
• Jacket:
• XLPE (XHHW-2 rated), 90°C wet/dry
Conductors
• UV sunlight resistant “SUN RES” (all colours) 3. Polypropylene FIllers
- Thermoplastic CPE black outer jacket (standard) 
rated: 90°C
• Oil Res I & II rated
4. Polyester Separator Tape
- Thermoset CPE (optional)
• (Direct burial rated
5. Thermoset CPE Protective Jacket
• Available in:
• -40°C cold bend rated

• Rated for use in hazardous locations:
- Custom insulation/jacket colours 
- Composite constructions
- Class I Zone 2 (Div 2)
-
TC-ER (optional)
- Class II Zone 20, 21 (Div 1)
-
Class II Zone 22 (Div 2)

Colour Coding

• Method K1 or K2 (standard) 
• Method 4 (optional)








Part Number
Number of Conductor Size NominalDiameterOverallCable CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull) 
Conductors (AWG/MCM) (in/mm) (kg/km) (30°C ambient) (Pulling Eye) (lb/kg) (in/mm)
2M010U140200400 2 14 0.372 / 9.45 75 / 111 25 66 / 30 3.3 / 85

2M010U140300400 3 14 0.392 / 9.96 94 / 140 25 99 / 45 3.5 / 90

2M010U140400400 4 14 0.426 / 10.83 117 / 174 20 132 / 60 3.8 / 97

2M010U140500400 5 14 0.465 / 11.81 138 / 205 20 165 / 75 4.2 / 106
2M010U140600400 6 14 0.505 / 12.83 162 / 241 20 197 / 90 4.5 / 115

2M010U140700400 7 14 0.505 / 12.83 177 / 264 17.5 230 / 104 4.5 / 115

2M010U140800400 8 14 0.575 / 14.6 218 / 325 17.5 263 / 119 5.2 / 131
2M010U141000400 10 14 0.668 / 16.97 270 / 402 12.5 329 / 149 6 / 153

2M010U141200400 12 14 0.688 / 17.48 309 / 460 12.5 395 / 179 6.2 / 157

2M010U141400400 14 14 0.722 / 18.35 352 / 524 12.5 461 / 209 6.5 / 165

2M010U141500400 15 14 0.741 / 18.83 373 / 556 12.5 494 / 224 6.7 / 169
2M010U142000400 20 14 0.841 / 21.36 483 / 719 12.5 658 / 298 7.6 / 192

2M010U142500400 25 14 0.974 / 24.74 628 / 935 11.25 823 / 373 8.8 / 223

2M010U143000400 30 14 1.028 / 26.12 726 / 1081 11.25 987 / 448 9.3 / 235

2M010U144000400 40 14 1.147 / 29.13 933 / 1389 10 1316 / 597 10.3 / 262
2M010U145000400 50 14 1.272 / 32.31 1145 / 1704 8.75 1645 / 746 11.4 / 291

2M010U120200400 2 12 0.408 / 10.36 98 / 146 30 104 / 47 3.7 / 93

2M010U120300400 3 12 0.431 / 10.94 127 / 189 30 157 / 71 3.9 / 98

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(3)(a) for number of Conductors.





1 800 668 4842 shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation