Page 38 - ShawFlex.com | UL Catalogue
P. 38


UL TRAY


V.2 | 38



TC
ZETABON UTILITY | MULTI-CONDUCTOR (600V) 
PAGE 1 OF 2 



ShawFlex Utility cables are the ideal choice for applications requiring an extra level of durability and noise 

protection in utility applications. The ZetabonM aluminum tape blocks any water, chemical or gaseous 
vapors from penetrating to the insulated conductors. It also provides mechanical strength for crush and 
impact protection. ZetabonM provides the additional benefit of shielding outside noise from adversely 
affecting the signal carried by the cables.


Voltage
Certifications/Compliances

600V
• UL 1277, Tray Cable (TC-ER)
Optional: 2000V
• UL 44, Thermoset Insulated Wires and Cables 1234 5
• IEEE 1202/383 (70,000 BTU/hr), Vertical

Product Construction
Flame Test rated
• Insulation:
• UL 1685/FT4, Vertical Tray Flame Test rated
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
-
FR XLPE (XHHW-2 rated) 
Test rated
1. Strand Bare (ASTM B8) Annealed Copper Conductors 
2. FR XLPE (XHHW-2 Rated) Insulated Conductors rated: 90°C wet/dry
• XLPE (RW90 rated), 90°C wet/dry
3. Polyester Separator Tape
-
VW-1 rated (optional)
• UV sunlight resistant “SUN RES” (all colours) 4. ZetabonTM Aluminum Tape
• Shielding:
• Direct burial rated
- ZetabonTM Aluminum Tape (standard)
• Exposed-Run (TC-ER) rated
5. CPE Outer Protective Jacket
• Jacket:
• -40°C cold bend rated
- Thermoplastic CPE outer black jacket 
• Rated for use in hazardous locations:
(standard)
- Class I Zone 2 (Div 2)
rated: 90°C
- Class II Zone 22 (Div 2)
- Thermoset CPE (optional)
• Available in:
Colour Coding
- Custom insulation/jacket colors 
• Method K1 & K2 (standard) - Composite constructions

• Method 4 (optional)


Each utility has its own unique speci cations. Please contract ShawFlex for product details

NominalDiameterOverall 
Conductor Size CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull)
Part Number NumberofConductors (AWG/MCM) Cable (kg/km) (30°C ambient) (Pulling Eye) (lb/kg) (in/mm) 
(in/mm)
2C410U140200409 2 14 0.412 / 10.46 98 / 146 25 66 / 30 7.4 / 188

2C410U140300409 3 14 0.432 / 10.97 116 / 172 25 99 / 45 7.8 / 198

2C410U140400409 4 14 0.467 / 11.85 138 / 206 20 132 / 60 8.4 / 213

2C410U140500409 5 14 0.505 / 12.83 161 / 239 20 165 / 75 9.1 / 231
2C410U140600409 6 14 0.575 / 14.6 200 / 298 20 197 / 90 10.3 / 263

2C410U140700409 7 14 0.575 / 14.6 214 / 318 17.5 230 / 104 10.3 / 263

2C410U140800409 8 14 0.615 / 15.62 242 / 361 17.5 263 / 119 11.1 / 281
2C410U141000409 10 14 0.708 / 17.98 296 / 441 12.5 329 / 149 12.7 / 324

2C410U141200409 12 14 0.728 / 18.49 332 / 494 12.5 395 / 179 13.1 / 333

2C410U141400409 14 14 0.762 / 19.37 376 / 559 12.5 461 / 209 13.7 / 349

2C410U141500409 15 14 0.781 / 19.84 396 / 589 12.5 494 / 224 14.1 / 357
2C410U142000409 20 14 0.921 / 23.39 538 / 800 12.5 658 / 298 16.6 / 421

2C410U142500409 25 14 1.014 / 25.76 647 / 963 11.25 823 / 373 18.3 / 464

2C410U143000409 30 14 1.069 / 27.14 741 / 1103 11.25 987 / 448 19.2 / 489

2C410U144000409 40 14 1.187 / 30.15 941 / 1400 10 1316 / 597 21.4 / 543
2C410U145000409 50 14 1.312 / 33.32 1142 / 1699 8.75 1645 / 746 23.6 / 600

2C410U120200409 2 12 0.448 / 11.38 121 / 180 30 104 / 47 8.1 / 205

2C410U120300409 3 12 0.471 / 11.96 152 / 226 30 157 / 71 8.5 / 215
2C410U120400409 4 12 0.51 / 12.95 181 / 269 24 209 / 95 9.2 / 233

2C410U120500409 5 12 0.584 / 14.83 233 / 346 24 261 / 118 10.5 / 267

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(3)(a) for number of Conductors.



1 800 668 4842 shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   36   37   38   39   40