ShawFlex VFD cables are the preferred power cables for AC Drives. These cables are primarily 

used between Pulse Width Modulation (PWM) inverters and AC motors. ShawFlex VFD
Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/ 
outdoor and ladder-type cable trays in wet/dry locations and are applicable in Industrial and 

Processing facilities.

Voltage
Certifications/Compliances
600V
• UL 1569, Metal Clad Cables (MC)

Optional: 2000V
• UL 44, Thermoset Insulated Wires and Cables 
• UL 1685/FT4, Vertical Tray Flame Test rated
5 
Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
• Insulation:
Flame Test rated
1234678 9

- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
rated: 90°C wet/dry Test rated
1. Tri-sectional Grounding Conductors
Shielding:
• XLPE (XHHW-2 rated), 90°C wet/dry
2. Stranded Bare (ASTM B8) Annealed Copper
- Dual helically applied copper tape shield
• UV sunlight resistant “SUN RES” (all colours) Conductors
3. FR XLPE (XHHW-2 Rated) Insulated Conductors
• Armour:
• (Direct burial rated
- Aluminum Interlocking Armor (AIA) (standard)
• -40°C cold bend rated
4. Polypropylene Fillers
- Steel Interlocking Armor (SIA) (optional)
• Rated for use in hazardous locations:
5. Polyester Separator Tape
• Jacket:
6. Dual Helically Applied Bare/Tinned Copper
- Class I Zone 2 (Div 2)
Tape Shield
- FR PVC inner black jacket
- Class II Zone 20, 21 (Div 1)
7. FR PVC Inner Protective Jacket
-
FRPVC outer black or yellow jacket (standard) -
Class II Zone 22 (Div 2)
8. Aluminum Interlocked Armor (AIA) (standard)
rated: 90°C to -40°C
9. FR PVC Outer Protective Jacket
Colour Coding
- Thermoset CPE optional) 
- Thermoplastic CPE (optional) • 3C – Black, # coded
-
Thermoplastic LSZH (optional)
• Available in:

- Custom insulation/jacket colours





Ground Max. Pulling Nominal Diameters
Number of ConductorSize Wire Size OD Over Cable Weight Ampacity Tension Min. Bend 
Conductors
(AWG/MCM)
(uninsulated) Inner Jacket (lbs/1000ft)/ (30°C ambient)
(Pulling Eye) Radius (Pull) Part Number
Over Armour Overall Cable 
(in/mm)
(kg/km)
(in/mm)
(in/mm)
(in/mm)
(AWG/MCM)
(lb/kg)
2C61HU1203007DR
3
12
16
0.439 / 11.14
0.678 / 17.23
0.798 / 20.28
386 / 574
30
157 / 71
14.4 / 365

2C61HU1003007DR 16.2 / 412
3
10
14
0.5 / 12.71
0.74 / 18.81
0.9 / 22.87
538 / 800
40
249 / 113

19 / 483
2C61HU0803007DR
3
8
14
0.657 / 16.69
0.897 / 22.79
1.057 / 26.86
769 / 1144
55
397 / 180

2C613U0603007DR 20.5 / 520
0.737 / 18.71
1.137 / 28.87
3
6
12
0.977 / 24.81
982 / 1462
75
629 / 285
21.6 / 549
2C613U0403007DR
3
4
12
0.838 / 21.28
1.042 / 26.46
1.202 / 30.52
1256 / 1870
95
1002 / 454

2C613U0203007DR 24.6 / 625
3
2
10
1.003 / 25.46
1.207 / 30.65
1.367 / 34.71
1755 / 2612
130
1593 / 723

26.9 / 683
2C613U0103407DR
3
1
10
1.129 / 28.69
1.334 / 33.87
1.493 / 37.93
2125 / 3163
145
2009 / 911
2C613U1/03407DR 28.4 / 722
3
1/0
10
1.215 / 30.87
1.42 / 36.06
1.579 / 40.12
2498 / 3717
170
2534 / 1150

30.1 / 764
2C613U2/03407DR
3
2/0
10
1.308 / 33.22
1.512 / 38.4
1.672 / 42.46
2922 / 4348
195
3194 / 1449

2C613U3/03407DR 33.1 / 842
3
3/0
8
1.417 / 36
1.622 / 41.19
1.842 / 46.78
3621 / 5389
225
4007 / 1818

35.3 / 897
2C613U4/03407DR
3
4/0
8
1.538 / 39.06
1.742 / 44.24
1.962 / 49.83
4296 / 6393
260
5078 / 2304
2C613U2503607DR 39.7 / 1008
3
250
8
1.68 / 42.67
1.985 / 50.41
2.205 / 56
5194 / 7730
290
6000 / 2722

44.8 / 1137
2C613U3503607DR
3
350
6
1.961 / 49.82
2.266 / 57.57
2.486 / 63.16
6960 / 10358
350
8400 / 3810

2C613U5003607DR
50.8 / 1290
3
500
6
2.236 / 56.81
2.542 / 64.55
2.822 / 71.67
9325 / 13877
430
12000 / 5443
2C613U7503607DR
3
750
4
2.686 / 68.22
2.991 / 75.96
3.271 / 83.08
13110 / 19509
535
18000 / 8165
58.9 / 1495


*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).