Page 36 - ShawFlex.com | UL Catalogue
P. 36


UL VFD


V.2 | 36



TC
TRAY | MULTI-CONDUCTOR (600V) 
PAGE 1 OF 1 



ShawFlex VFD cables are the preferred power cables for AC Drives. These cables are primarily 

used between Pulse Width Modulation (PWM) inverters and AC motors. ShawFlex VFD
Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor/ 
outdoor and ladder-type cable trays in wet/dry locations and are applicable in Industrial and 

Processing facilities.

Voltage
Certifications/Compliances
600V
• UL 1277, Tray Cable (TC-ER)

Optional: 2000V
• UL 44, Thermoset Insulated Wires and Cables 
• UL1685/FT4,VerticalTrayFlameTestrated
Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
12345 6
Flame Test rated (optional)
• Insulation:
- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
rated: 90°C wet/dry
Test rated
1.
Stranded Bare (ASTM B8) Annealed Copper 
-
• XLPE (XHHW-2 rated), 90°C wet/dry
Conductors
• UV sunlight resistant “SUN RES” (all colours) 2. FR XLPE (XHHW-2 Rated) Insulated Conductors 
• Shielding:
3. Tri-sectional Grounding Conductors 
- Dual helically applied copper tape shield
• (Direct burial rated
• Jacket:
• -40°C cold bend rated
4. Polypropylene Fillers
• Rated for use in hazardous locations:
5.
Dual Helically Applied Bare/Tinned Copper -
FR PVC outer black or yellow jacket (standard) 
Tape Shield
- Class I Zone 2 (Div 2)
6.
FR PVC Outer Protective Jacket
rated: 90°C to -40°C
- - Class II Zone 20, 21 (Div 1)
Thermoset CPE optional) 
-
-
Class II Zone 22 (Div 2)
Thermoplastic CPE (optional) 
Thermoplastic LSZH (optional)
-
Colour Coding
• Available in:
• 3C – Black, # coded
- Custom insulation/jacket colours 
- TC-ER (optional)








Ground 
Number of ConductorSize Wire Size Nominal Diameter Cable Weight (lb- Ampacity Max. Pulling Tension Min. Bend Radius (Pull) 
Part Number
Overall cable 
Conductors
(AWG/MCM)
(uninsulated) (in/mm)
s/1000ft)/(kg/km)
(30°C ambient)
(Pulling Eye) (lb/kg)
(in/mm)
(AWG/MCM)

2C01HU1203007DR
3
12
16
0.439 / 11.14
166 / 247
30
157 / 71
7.9 / 201
2C01HU1003007DR 9 / 229
3
10
14
0.5 / 12.71
247 / 368
40
249 / 113

11.8 / 300
2C01HU0803007DR
3
8
14
0.657 / 16.69
376 / 560
55
397 / 180

2C013U0603007DR 13.3 / 337
3
6
12
0.737 / 18.71
524 / 780
75
629 / 285
15.1 / 383
2C013U0403007DR
3
4
12
0.838 / 21.28
714 / 1063
95
1002 / 454

2C013U0203007DR 18 / 458
1074 / 1598
3
2
10
1.003 / 25.46
130
1593 / 723

20.3 / 516
2C013U0103407DR
3
1
10
1.129 / 28.69
1298 / 1932
145
2009 / 911

2C013U1/03407DR 21.9 / 556
3
1/0
10
1.215 / 30.87
1563 / 2326
170
2534 / 1150
23.5 / 598
2C013U2/03407DR
3
2/0
10
1.308 / 33.22
1864 / 2773
195
3194 / 1449

2C013U3/03407DR 25.5 / 648
3
3/0
8
1.418 / 36
2301 / 3425
225
4007 / 1818

27.7 / 703
2C013U4/03407DR
3
4/0
8
1.538 / 39.06
2784 / 4143
260
5078 / 2304
2C013U2503607DR 30.2 / 768
3
250
8
1.68 / 42.67
3240 / 4821
290
6000 / 2722

35.3 / 897
2C013U3503607DR
3
350
6
1.961 / 49.82
4538 / 6753
350
8400 / 3810

2C013U5003607DR
40.3 / 1023
3
500
6
2.236 / 56.81
6128 / 9120
430
12000 / 5443

2C013U7503607DR
3
750
4
2.686 / 68.22
8729 / 12990
535
18000 / 8165
48.3 / 1228

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).







shawcor.com
1 800 668 4842
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation