Page 35 - ShawFlex.com | UL Catalogue
P. 35


UL METAL CLAD


V.2 | 35




AIA POWER | SINGLE CONDUCTOR (2000V) 
PAGE 1 OF1



Metal Clad AIA Power cables are suitable for use in ventilated, non-ventilated and ladder 

type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp 
or dry locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

2000V • UL 1569, Metal Clad Cables (MC)
24 
Optional: 600V
• UL 44, Thermoset Insulated Wires and Cables 
• UL1685/FT4,VerticalTrayFlameTestrated
13567

Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
• Insulation:
Flame Test rated
- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame 
1.
Strand Bare (ASTM B8) Annealed Copper Conductor 
rated: 90°C wet/dry
Test rated 
• Armor:
2. • XLPE (XHHW-2 rated), 90°C wet/dry FR XLPE (XHHW-2 Rated) Insulated Conductor 
- Aluminum Interlocked Armor (AIA) (standard)
3. • UV sunlight resistant “SUN RES” (all colours) (for Serve/Wound Grounds
• Jacket:
4.
CT use) Polyester Separator Tape
5. FR PVC Inner Protective Jacket 
• Direct burial rated -
FR PVC inner/outer black jacket 
6. • -40°C cold bend rated rated: 90°C to -40°C
Aluminum Interlocked Armor (AIA) 
7. • Rated for use in hazardous locations:
- FR PVC Outer Protective Jacket
Thermoset CPE optional) 
-
Thermoplastic CPE (optional) - Class I Zone 2 (Div 2)

Thermoplastic LSZH (optional)
- Class II Zone 20, 21 (Div 1)
-
-
Class II Zone 22 (Div 2)
• Available in:
- Custom insulation/jacket colours 
Colour Coding
- Composite constructions
• Black conductors (standard)


Ground Nominal Diameters
Max. Pulling 
ODOverInner Cable Weight 
Part Number
Number of ConductorSize Wire Size Jacket (in/ (lbs/1000ft)/ Ampacity Tension Min.BendRadius(Pull) 
Conductors
(AWG/MCM)
(uninsulated) mm)(
Over Armour (kg/km)
(30°Cambient)
(Pulling Eye) (in/mm)
Overall Cable 
(AWG/MCM)
(in/mm)
(lb/kg)
(in/mm)

2K610U080100700
1
8
18
0.457 / 11.61
0.697 / 17.7
0.809 / 20.55
334 / 498
55
132 / 60
14.6 / 370
2K610U060100700 1
6
16
0.516 / 13.11
0.756 / 19.2
0.868 / 22.05
423 / 630
75
210 / 95
15.6 / 397

16.8 / 427
2K610U040100700
1
4
16
0.583 / 14.81
0.823 / 20.9
0.935 / 23.75
509 / 757
95
334 / 151

2K610U030100700 17.3 / 440
1
3
16
0.61 / 15.49
0.85 / 21.59
0.962 / 24.43
556 / 827
115
421 / 191

17.9 / 454
2K610U020100700
1
2
16
0.641 / 16.28
0.881 / 22.38
0.993 / 25.22
613 / 912
130
531 / 241
2K610U010140700 19.8 / 502
1
1
14
0.746 / 18.95
0.986 / 25.04
1.098 / 27.89
778 / 1157
145
670 / 304

19.8 / 504
2K610U1/0140700
1
1/0
14
0.786 / 19.96
0.99 / 25.15
1.102 / 27.99
859 / 1278
170
845 / 383

2K610U2/0140700 20.6 / 523
1
2/0
14
0.829 / 21.06
1.033 / 26.24
1.145 / 29.08
966 / 1438
195
1065 / 483
21.5 / 547
2K610U3/0140700
1
3/0
14
0.88 / 22.35
1.084 / 27.53
1.196 / 30.38
1127 / 1678
225
1336 / 606

2K610U4/0140700 22.5 / 572
1
4/0
14
0.936 / 23.77
1.14 / 28.96
1.252 / 31.8
1346 / 2004
260
1693 / 768

23.9 / 607
2K610U250160700
1
250
14
1.012 / 25.7
1.216 / 30.89
1.328 / 33.73
1506 / 2241
290
2000 / 907

2K610U300160700 24.9 / 631
1
300
14
1.065 / 27.05
1.269 / 32.23
1.381 / 35.08
1744 / 2596
320
2400 / 1089
25.8 / 654
2K610U350160700
1
350
14
1.115 / 28.32
1.319 / 33.5
1.431 / 36.35
1926 / 2867
350
2800 / 1270

2K610U500160700
28.1 / 713
1
500
14
1.243 / 31.57
1.447 / 36.75
1.559 / 39.6
2530 / 3765
430
4000 / 1814

2K610U750160700
1
750
14
1.452 / 36.88
1.656 / 42.06
1.788 / 45.42
3578 / 5324
535
6000 / 2722
32.2 / 817

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).













1 800 668 4842
shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   33   34   35   36   37