Page 34 - ShawFlex.com | UL Catalogue
P. 34


UL METAL CLAD


V.2 | 34




AIA POWER | SINGLE CONDUCTOR (600V) 
PAGE 1 OF1



Metal Clad AIA Power cables are suitable for use in ventilated, non-ventilated and ladder 

type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp 
or dry locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

600V
• UL 1569, Metal Clad Cables (MC)
24 
Optional: 2000V
• UL 44, Thermoset Insulated Wires and Cables 
• UL1685/FT4,VerticalTrayFlameTestrated
13567

Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
• Insulation:
Flame Test rated
- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame 
1.
Strand Bare (ASTM B8) Annealed Copper Conductor 
rated: 90°C wet/dry
Test rated 
• Armor:
2. • XLPE (XHHW-2 rated), 90°C wet/dry FR XLPE (XHHW-2 Rated) Insulated Conductor 
- Aluminum Interlocked Armor (AIA) (standard)
3. • UV sunlight resistant “SUN RES” (all colours) (for Serve/Wound Grounds
• Jacket:
4.
CT use) Polyester Separator Tape
5. FR PVC Inner Protective Jacket 
• Direct burial rated -
FR PVC inner/outer black jacket 
6. • -40°C cold bend rated rated: 90°C to -40°C
Aluminum Interlocked Armor (AIA) 
7. • Rated for use in hazardous locations:
- Thermoset CPE optional) FR PVC Outer Protective Jacket
-
Thermoplastic CPE (optional) - Class I Zone 2 (Div 2)

Thermoplastic LSZH (optional)
-
- Class II Zone 20, 21 (Div 1)
• Available in:
-
Class II Zone 22 (Div 2)
- Custom insulation/jacket colours 
Colour Coding
-
Composite constructions
• Black conductors (standard)



Ground OD Over Nominal Diameters
Cable Weight Max. Pulling Min. Bend Radius Ampacity 
Part Number
Number of ConductorSize Wire Size Inner Jacket (lbs/1000ft)/ Tension (Pull) (30°C 
Conductors
(AWG/MCM)
(uninsulated) (in/mm)(
(kg/km)
(Pulling Eye) (in/mm)
Over Armour Overall Cable ambient)
(AWG/MCM)
(lb/kg)
(in/mm)
(in/mm)

1
0.407 / 10.34
2C610U080100700
8
18
0.647 / 16.43
0.759 / 19.28
307 / 457
55
132 / 60
13.7 / 347

2C610U060100700 14.7 / 374
6
0.706 / 17.93
1
16
0.466 / 11.84
0.818 / 20.78
394 / 587
75
210 / 95
15.6 / 395
2C610U040100700
4
0.753 / 19.13
0.865 / 21.97
462 / 687
1
16
0.513 / 13.03
95
334 / 151

2C610U030100700 16.4 / 417
1
3
16
0.56 / 14.22
0.8 / 20.32
0.912 / 23.16
522 / 777
115
421 / 191

17 / 431
2C610U020100700
1
2
16
0.591 / 15.01
0.831 / 21.11
0.943 / 23.95
578 / 860
130
531 / 241
2C610U010140700 18.5 / 470
1
1
14
0.676 / 17.17
0.916 / 23.27
1.028 / 26.11
725 / 1079
145
670 / 304

19.2 / 488
2C610U1/0140700
1
1/0
14
0.716 / 18.19
0.956 / 24.28
1.068 / 27.13
811 / 1207
170
845 / 383

2C610U2/0140700 19.6 / 499
1
2/0
14
0.759 / 19.28
0.979 / 24.87
1.091 / 27.71
911 / 1356
195
1065 / 483

20.3 / 515
2C610U3/0140700
1
3/0
14
0.81 / 20.57
1.014 / 25.76
1.126 / 28.6
1066 / 1587
225
1336 / 606
2C610U4/0140700 21.3 / 540
1
4/0
14
0.866 / 22
1.07 / 27.18
1.182 / 30.02
1282 / 1908
260
1693 / 768

22.5 / 571
250
2C610U250160700
1
14
0.932 / 23.67
1.136 / 28.85
1.248 / 31.7
1427 / 2124
290
2000 / 907

2C610U300160700 23.4 / 595
1
300
14
0.985 / 25.02
1.189 / 30.2
1.301 / 33.05
1660 / 2471
320
2400 / 1089

24.3 / 618
2C610U350160700
1
350
14
1.035 / 26.29
1.239 / 31.47
1.351 / 34.32
1839 / 2737
350
2800 / 1270
2C610U500160700
26.6 / 676
1
500
14
1.163 / 29.54
1.367 / 34.72
1.479 / 37.57
2433 / 3620
430
4000 / 1814

2C610U750160700
1
750
14
1.372 / 34.85
1.576 / 40.03
1.708 / 43.38
3461 / 5151
535
6000 / 2722
30.7 / 781

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).













1 800 668 4842