Page 32 - ShawFlex.com | UL Catalogue
P. 32


UL METAL CLAD


V.2 | 32




AIA POWER | MULTI-CONDUCTOR (2000V) 
PAGE 1 OF 2



Metal Clad AIA Power cables are suitable for use in ventilated, non-ventilated and ladder 

type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp 
or dry locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

2000V • UL 1569, Metal Clad Cables (MC)
Optional: 600V
• UL 44, Thermoset Insulated Wires and Cables 
• UL1685/FT4,VerticalTrayFlameTestrated
123456

Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
• Insulation:
Flame Test rated
- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame

rated: 90°C wet/dry
Test rated
1. Grounding/Bonding Conductor
• Armor:
• XLPE (XHHW-2 rated), 90°C wet/dry
2. Strand Bare (ASTM B8) Annealed Copper Conductors 
- Aluminum Interlocked Armor (AIA) (standard) • UV sunlight resistant “SUN RES” (all colours) (for
3. FR XLPE (XHHW-2 Rated) Insulated Conductors 
- Steel Interlocked Armor (SIA) (optional)
CT use)
4. Polyester Separator Tape

- Served Wire Armor (SWA) (optional)
• Direct burial rated
5. Aluminum Interlocked Armor (AIA)
- Zetabon (optional)
• -40°C cold bend rated
6. FR PVC Outer Protective Black Jacket
• Jacket:
• Rated for use in hazardous locations:
- Class I Zone 2 (Div 2)
-
FR PVC outer black jacket 

- Class II Zone 22 (Div 2)
rated: 90°C to -40°C
- Thermoset CPE optional) 
Colour Coding
-
Thermoplastic CPE (optional) 
• Method K1 or K2 (standard) 
Thermoplastic LSZH (optional)
-
• Method 4 (optional)
• Available in:
- Custom insulation/jacket colours 
- Composite constructions

-
Inner jacket optional





Number of Conductor Size GroundWireSize Nominal Diameter Nominal Diameter Cable Weight (lb- Ampacity Max.PullingTension Min. Bend Radius
Part Number Overall Cable (Pull) 
Conductors (AWG/MCM) (AWG/MCM) Over Armor s/1000ft)/(kg/km) (30°C ambient) (PullingEye)(lb/kg) (in/mm) (in/mm)

2K610U140200709 2 14 14 0.63 / 16 0.742 / 18.85 227 / 337 25 66 / 30 13.4 / 339

2K610U120200709 2 12 12 0.666 / 16.92 0.778 / 19.76 265 / 394 30 104 / 47 14 / 356
2K610U100200709 2 10 10 0.716 / 18.19 0.828 / 21.03 321 / 478 40 166 / 75 14.9 / 379

2K610U080200709 2 8 10 0.814 / 20.68 0.926 / 23.52 403 / 599 55 265 / 120 16.7 / 423

2K610U060200709 2 6 8 0.892 / 22.66 1.004 / 25.5 516 / 768 75 419 / 190 18.1 / 459

2K610U040200709 2 4 8 0.986 / 25.04 1.098 / 27.89 659 / 981 95 668 / 303 19.8 / 502
2K610U030200709 2 3 6 1.004 / 25.5 1.116 / 28.35 778 / 1158 115 842 / 382 20.1 / 510

2K610U020200709 2 2 6 1.066 / 27.08 1.178 / 29.92 894 / 1330 130 1062 / 482 21.2 / 539

2K610U010240709 2 1 6 1.224 / 31.09 1.336 / 33.93 1103 / 1642 145 1339 / 607 24 / 611
2K610U1/0240709 2 1/0 6 1.304 / 33.12 1.416 / 35.97 1294 / 1926 170 1690 / 766 25.5 / 647

2K610U2/0240709 2 2/0 6 1.39 / 35.31 1.502 / 38.15 1520 / 2261 195 2130 / 966 27 / 687

2K610U3/0240709 2 3/0 4 1.492 / 37.9 1.604 / 40.74 1847 / 2749 225 2671 / 1212 28.9 / 733

2K610U4/0240709 2 4/0 4 1.604 / 40.74 1.736 / 44.09 2230 / 3318 260 3386 / 1536 31.2 / 794
2K610U250260709 2 250 4 1.756 / 44.6 1.888 / 47.96 2575 / 3831 290 4000 / 1814 34 / 863

2K610U300260709 2 300 3 1.963 / 49.86 2.095 / 53.21 3182 / 4736 320 4800 / 2177 37.7 / 958

2K610U350260709 2 350 3 2.063 / 52.4 2.195 / 55.75 3579 / 5326 350 5600 / 2540 39.5 / 1004

2K610U500260709 2 500 3 2.319 / 58.9 2.481 / 63.02 4806 / 7153 430 8000 / 3629 44.7 / 1134
2K610U140300709 3 14 14 0.674 / 17.13 0.786 / 19.97 262 / 390 25 99 / 45 14.2 / 360

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).



1 800 668 4842
shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   30   31   32   33   34