Metal Clad AIA Control cables are suitable for use in ventilated, non-ventilated and ladder 

type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp 
or dry locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

2000V • UL 1569, Metal Clad Cables (MC)
Optional: 600V
• UL 44, Thermoset Insulated Wires and Cables 1 2
3 4 5
• UL1685/FT4,VerticalTrayFlameTestrated

Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical
• Insulation:
Flame Test rated
- FR XLPE (XHHW-2 rated)
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame

rated: 90°C wet/dry
Test rated
1. Grounding/Bonding Conductor
• Armor:
• XLPE (XHHW-2 rated), 90°C wet/dry
2. Strand Bare (ASTM B8) Annealed Copper Conductors 
- Aluminum Interlocked Armor (AIA) (standard) • UV sunlight resistant “SUN RES” (all colours) (for
3. FR XLPE (XHHW-2 Rated) Insulated Conductors 
- Steel Interlocked Armor (SIA) (optional)
CT use)
4. Polyester Separator Tape

- Served Wire Armor (SWA) (optional)
• Direct burial rated
5. Aluminum Interlocked Armor (AIA)
- Zetabon (optional)
• -40°C cold bend rated
6. FR PVC Outer Protective Black Jacket
• Jacket:
• Rated for use in hazardous locations:
- Class I Zone 2 (Div 2)
-
FR PVC outer black jacket 

- Class II Zone 22 (Div 2)
rated: 90°C to -40°C
- Thermoset CPE optional) 
Colour Coding
-
Thermoplastic CPE (optional) 
• Method1 K1 or K2 (standard) 
Thermoplastic LSZH (optional)
-
• Method 4 (optional)
• Available in:
- Custom insulation/jacket colours 
- Composite constructions



Max. Pulling 
Ground Wire Number of Conductor Size Nominal Diameter Nominal Diameter Cable Weight (lb- Ampacity Tension Min. Bend Radius 
Part Number Size
Conductors (AWG/MCM) Over Armor
Overall Cable s/1000ft)/(kg/km)
(30°C ambient)
(Pulling Eye) (lb/ (Pull) 
(AWG/MCM)
(in/mm)
kg)
(in/mm)

2K610U140200709 2 14 14 0.63 / 16 0.742 / 18.85 227 / 337 25 66 / 30 13.4 / 339

2K610U140300709 3 14 14 0.674 / 17.13 0.786 / 19.97 262 / 390 25 99 / 45 14.2 / 360

2K610U140400709 4 14 14 0.723 / 18.36 0.835 / 21.2 295 / 438 20 132 / 60 15 / 382
2K610U140500709 5 14 14 0.765 / 19.43 0.877 / 22.28 334 / 496 20 165 / 75 15.8 / 401

2K610U140600709 6 14 14 0.823 / 20.9 0.935 / 23.75 380 / 565 20 197 / 90 16.8 / 427

2K610U140700709 7 14 14 0.881 / 22.37 0.993 / 25.22 425 / 632 17.5 230 / 104 17.9 / 454

2K610U140800709 8 14 14 0.941 / 23.89 1.053 / 26.74 473 / 703 17.5 263 / 119 18.9 / 481
2K610U141000709 10 14 14 0.98 / 24.89 1.092 / 27.74 532 / 792 12.5 329 / 149 19.7 / 499

2K610U141200709 12 14 14 1.009 / 25.63 1.121 / 28.47 591 / 879 12.5 395 / 179 20.2 / 513

2K610U141400709 14 14 14 1.059 / 26.9 1.171 / 29.75 658 / 980 12.5 461 / 209 21.1 / 535
2K610U141500709 15 14 14 1.086 / 27.59 1.198 / 30.43 693 / 1032 12.5 494 / 224 21.6 / 548

2K610U142000709 20 14 14 1.231 / 31.26 1.343 / 34.11 866 / 1289 12.5 658 / 298 24.2 / 614

2K610U142500709 25 14 14 1.366 / 34.7 1.478 / 37.54 1044 / 1553 11.25 823 / 373 26.6 / 676

2K610U143000709 30 14 14 1.445 / 36.71 1.557 / 39.55 1190 / 1770 11.25 987 / 448 28 / 712
2K610U144000709 40 14 14 1.617 / 41.07 1.749 / 44.42 1545 / 2299 10 1316 / 597 31.5 / 800

2K610U145000709 50 14 14 1.798 / 45.68 1.93 / 49.03 1861 / 2769 8.75 1645 / 746 34.7 / 883

2K610U120200709 2 12 12 0.666 / 16.92 0.778 / 19.76 265 / 394 30 104 / 47 14 / 356

2K610U120300709 3 12 12 0.715 / 18.15 0.827 / 21 310 / 461 30 157 / 71 14.9 / 378

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(3)(a) for number of Conductors.