Page 20 - ShawFlex.com | UL Catalogue
P. 20


UL TRAY


V.2 | 20



TC
CONTROL | MULTI-CONDUCTOR (2000V) 
PAGE 1 OF 2 



Tray Control cables are suitable for use in ventilated, non-ventilated and ladder type cable 

trays, direct burial, raceways and for exposed or concealed wiring in wet, damp or dry 
locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

2000V
• UL 1277, Tray Cable (TC)-ER (optional)
• UL 44, Thermoset Insulated Wires and Cables 
12345
Product Construction
• UL1685/FT4, Vertical Tray Flame Test rated
• Insulation:
• IEEE 1202/383 (70,000 BTU/hr), Vertical
- FR XLPE (RHW-2 rated)
Flame Test rated (optional)
rated: 90°C wet/dry • ICEA T-30-520 (70,000 BTU/hr), Vertical Flame

• Jacket:
Test rated
1. Grounding/Bonding Conductor
• XLPE (XHHW-2 rated), 90°C wet/dry
2. Strand Bare (ASTM B8) Annealed Copper Conductors -
FR PVC outer black jacket 
• UV sunlight resistant “SUN RES” (all colours) 3. FR XLPE (RHW-2 Rated) Insulated Conductors rated: 90°C to -40°C
• Direct burial rated
4. Polypropylene Fillers
- Thermoset CPE (optional) 
• -40°C cold bend rated
5. Polyester Separator Tape
- Thermoplastic CPE (optional) 
• Rated for use in hazardous locations:
6. FR PVC Outer Protective Jacket
-
Thermoplastic LSZH (optional)
- Class I Zone 2 (Div 2)
• Available in:
- Class II Zone 22 (Div 2)
- Custom insulation/jacket colors 
- Composite constructions
Colour Coding
• Method K1 & K2 (standard) 

• Method 4 (optional)






NominalDiameterOverall 
Conductor Size CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull)
Part Number NumberofConductors Cable 
(AWG/MCM) (kg/km) (30°C ambient) (Pulling Eye) (lb/kg) (in/mm) (in/mm)

2K010U140200700 2 14 0.492 / 12.5 111 / 165 25 66 / 30 4.4 / 112

2K010U140300700 3 14 0.521 / 13.23 137 / 204 25 99 / 45 4.7 / 119

2K010U140400700 4 14 0.601 / 15.27 188 / 280 20 132 / 60 5.4 / 137
2K010U140500700 5 14 0.657 / 16.69 227 / 338 20 165 / 75 5.9 / 150

2K010U140600700 6 14 0.715 / 18.16 261 / 388 20 197 / 90 6.4 / 163

2K010U140700700 7 14 0.715 / 18.16 282 / 420 17.5 230 / 104 6.4 / 163
2K010U140800700 8 14 0.773 / 19.63 315 / 469 17.5 263 / 119 7 / 177

2K010U141000700 10 14 0.948 / 24.08 428 / 637 12.5 329 / 149 8.5 / 217

2K010U141200700 12 14 0.977 / 24.82 483 / 719 12.5 395 / 179 8.8 / 223

2K010U141400700 14 14 1.027 / 26.09 548 / 815 12.5 461 / 209 9.2 / 235
2K010U141500700 15 14 1.054 / 26.78 580 / 863 12.5 494 / 224 9.5 / 241

2K010U142000700 20 14 1.199 / 30.45 747 / 1111 12.5 658 / 298 10.8 / 274

2K010U142500700 25 14 1.334 / 33.88 908 / 1351 11.25 823 / 373 12 / 305
2K010U143000700 30 14 1.413 / 35.89 1048 / 1559 11.25 987 / 448 12.7 / 323

2K010U144000700 40 14 1.585 / 40.26 1344 / 2000 10 1316 / 597 14.3 / 362

2K010U145000700 50 14 1.826 / 46.39 1756 / 2613 8.75 1645 / 746 16.4 / 417

2K010U120200700 2 12 0.528 / 13.41 136 / 202 30 104 / 47 4.8 / 121
2K010U120300700 3 12 0.59 / 14.98 189 / 282 30 157 / 71 5.3 / 135

2K010U120400700 4 12 0.645 / 16.37 235 / 349 24 209 / 95 5.8 / 147

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(3)(a) for number of Conductors.