Page 16 - ShawFlex.com | UL Catalogue
P. 16


UL TRAY


V.2 | 16



TC
CONTROL | MULTI-CONDUCTOR (600V) 
PAGE 1 OF 2 



Tray Control cables are suitable for use in ventilated, non-ventilated and ladder type cable 

trays, direct burial, raceways and for exposed or concealed wiring in wet, damp or dry 
locations in -40°C (-40°F) environments. Applicable for use in Utilities, Industrial and 
Commercial applications.


Voltage
Certifications/Compliances

600V
• UL 1277, Tray Cable (TC-ER)
• UL 44, Thermoset Insulated Wires and Cables 
12345
Product Construction
• UL 1685/FT4, Vertical Tray Flame Test rated
• Insulation:
• IEEE 1202/383 (70,000 BTU/hr), Vertical
- FR XLPE (XHHW-2 rated)
Flame Test rated (optional)
rated: 90°C wet/dry
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame

- VW-1 rated (optional)
Test rated
1. Strand Bare (ASTM B8) Annealed Copper Conductors 
• Armor:
• XLPE (XHHW-2 rated), 90°C wet/dry
2. FR XLPE (XHHW-2 Rated) Insulated Conductors 
- Zetabon (optional)
• UV sunlight resistant “SUN RES” (all colours) 3. Polypropylene Fillers
• Direct burial rated
4. Polyester Separator Tape
• Jacket:
• -40°C cold bend rated
5. FR PVC Outer Protective Jacket
-
FR PVC outer black jacket 
• Rated for use in hazardous locations:
rated: 90°C to -40°C
- Class I Zone 2 (Div 2)
- Thermoset CPE (optional) 
- Class II Zone 22 (Div 2)
- Thermoplastic CPE (optional) 
-
Thermoplastic LSZH (optional)
Colour Coding
• Available in:
• Method K1 & K2 (standard) - Custom insulation/jacket colors 

• Method 4 (optional)
- Composite constructions









Part Number
Number of Conductor Size NominalDiameterOverallCable CableWeight(lbs/1000ft)/ Ampacity Max. Pulling Tension Min. Bend Radius (Pull) 
Conductors (AWG/MCM) (in/mm) (kg/km) (30°C ambient) (Pulling Eye) (lb/kg) (in/mm)

2C010U140200700 2 14 0.372 / 9.45 72 / 108 25 66 / 30 3.3 / 85

2C010U140300700 3 14 0.392 / 9.96 90 / 134 25 99 / 45 3.5 / 90
2C010U140400700 4 14 0.426 / 10.83 111 / 166 20 132 / 60 3.8 / 97

2C010U140500700 5 14 0.465 / 11.81 130 / 194 20 165 / 75 4.2 / 106

2C010U140600700 6 14 0.505 / 12.83 153 / 228 20 197 / 90 4.5 / 115
2C010U140700700 7 14 0.505 / 12.83 167 / 249 17.5 230 / 104 4.5 / 115

2C010U140800700 8 14 0.575 / 14.6 207 / 308 17.5 263 / 119 5.2 / 131

2C010U141000700 10 14 0.668 / 16.97 256 / 381 12.5 329 / 149 6 / 153

2C010U141200700 12 14 0.688 / 17.48 291 / 433 12.5 395 / 179 6.2 / 157
2C010U141400700 14 14 0.722 / 18.35 331 / 493 12.5 461 / 209 6.5 / 165

2C010U141500700 15 14 0.741 / 18.83 351 / 522 12.5 494 / 224 6.7 / 169

2C010U142000700 20 14 0.841 / 21.36 453 / 674 12.5 658 / 298 7.6 / 192
2C010U142500700 25 14 0.974 / 24.74 590 / 878 11.25 823 / 373 8.8 / 223

2C010U143000700 30 14 1.028 / 26.12 680 / 1012 11.25 987 / 448 9.3 / 235

2C010U144000700 40 14 1.147 / 29.13 871 / 1296 10 1316 / 597 10.3 / 262

2C010U145000700 50 14 1.272 / 32.31 1067 / 1588 8.75 1645 / 746 11.4 / 291
2C010U120200700 2 12 0.408 / 10.36 95 / 141 30 104 / 47 3.7 / 93

2C010U120300700 3 12 0.431 / 10.94 122 / 182 30 157 / 71 3.9 / 98

2C010U120400700 4 12 0.47 / 11.94 150 / 224 24 209 / 95 4.2 / 107

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(3)(a) for number of Conductors.



1 800 668 4842 shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation

   14   15   16   17   18