Page 14 - ShawFlex.com | UL Catalogue
P. 14


UL TRAY


V.2 | 14



TC
INSTRUMENTATION | PAIRS & TRIADS (600V) 
PAGE 1 OF 2 



Tray Instrumentation cables can be used to minimize noise and singal interference by 
preventing crosstalk between pairs and triads. This cable can also be used to carry analogue 

or digital signals. Tray Instrumentation cables can be installed in raceways, direct burial 
applications and in outdoor exposed industrial applications.

Voltage
Certifications/Compliances

600V
• UL 1277, Tray Cable (TC-ER)
5
• UL 44, Thermoset Insulated Wires and Cables 1 2
3 4
6
Product Construction
• UL 1685/FT4, Vertical Tray Flame Test rated
• Insulation:
• IEEE 1202/383 (70,000 BTU/hr), Vertical
- FR XLPE (XHHW-2 rated)
Flame Test rated (optional)
rated: 90°C wet/dry
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame

- VW-1 rated (optional)
Test rated
1. Stranded Bare Copper Conductors (Tinned 
• Shielding (foil-free edge):
• XLPE (XHHW-2 rated), 90°C wet/dry
- ISOS (standard)
• UV sunlight resistant “SUN RES” (all colours) Available)
- OS (optional)
• Direct burial rated
2. FR XLPE (XHHW-2 rated) Insulated Conductors 
3. Individual Shield & Overall Shielded Pairs/
• Armor:
• -40°C cold bend rated
Triads with Tinned Copper Drain Wire
- Zetaon (optional)
• Rated for use in hazardous locations:
• Jacket:
- Class I Zone 2 (Div 2)
4. Polyester Separator Tape
- Class II Zone 22 (Div 2)
-
FR PVC outer black jacket 5. Overall Aluminum/Mylar Shield with Tinned
Copper Drain Wire
rated: 90°C to -40°C
6. FR PVC Protective Jacket
- Thermoset CPE (optional) 
Colour Coding
- Thermoplastic CPE (optional) 
• Pairs - Black, & white, with black printing on -
Thermoplastic LSZH (optional)

white (standard)
• Available in:
• Triads - Black, white & red, with black printing - Custom insulation/jacket colors 
on white (standard)
- Composite constructions



PAIRS


OD Over 
Conductor Size Cable Weight (lbs/1000ft)/ Max. Pulling Tension Min. Bend Radius (Pull)
Part Number Number of Pairs (AWG/MCM) Inner Jacket (kg/km) (Pulling Eye) (lb/kg) (in/mm) 
(in/mm)
2C021U160100700 1 16 0.347 / 8.81 60 / 89 41 / 19 6.2 / 159

2C022U160200700 2 16 0.514 / 13.06 126 / 187 82 / 37 9.3 / 235

2C022U160400700 4 16 0.632 / 16.06 199 / 296 165 / 75 11.4 / 289

2C022U160600700 6 16 0.756 / 19.21 282 / 420 247 / 112 13.6 / 346
2C022U160800700 8 16 0.821 / 20.86 349 / 519 330 / 150 14.8 / 375

2C022U161200700 12 16 1.042 / 26.46 534 / 795 494 / 224 18.7 / 476
2C022U161600700 16 16 1.16 / 29.46 667 / 993 659 / 299 20.9 / 530

2C022U162400700 24 16 1.438 / 36.54 963 / 1433 989 / 449 25.9 / 658

2C022U163600700 36 16 1.657 / 42.09 1353 / 2013 1483 / 673 29.8 / 758
2C021U180100700 1 18 0.323 / 8.2 49 / 73 26 / 12 5.8 / 148

2C022U180200700 2 18 0.475 / 12.06 100 / 149 52 / 24 8.5 / 217

2C022U180400700 4 18 0.584 / 14.84 156 / 232 104 / 47 10.5 / 267
2C022U180600700 6 18 0.696 / 17.68 218 / 324 156 / 71 12.5 / 318

2C022U180800700 8 18 0.754 / 19.16 266 / 396 208 / 94 13.6 / 345
2C022U181200700 12 18 0.957 / 24.32 407 / 605 312 / 142 17.2 / 438

2C022U181800700 18 18 1.122 / 28.5 559 / 832 468 / 212 20.2 / 513

2C022U182400700 24 18 1.315 / 33.41 719 / 1070 624 / 283 23.7 / 601
2C022U183600700 36 18 1.512 / 38.42 996 / 1482 936 / 425 27.2 / 692








1 800 668 4842
shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation