Page 10 - ShawFlex.com | UL Catalogue
P. 10


UL PLTC


V.2 | 10




TRAY THERMOCOUPLE EXTENSION | PAIRS (300V) 
PAGE 1 OF 1



ShawFlex Thermocouple Extension cables offer advantages in cost and mechanical properties 

when used for connections between thermocouples and instruments.

Voltage
Certifications/Compliances
300 V • UL 13, Power Limited Tray Cable (PLTC)

Optional: 600V
• UL 2250, Instrumentation Tray Cable (ITC)
• UL 83, Thermoplastic Insulated WIres and Cables 
Product Construction
• IEEE 1202/383 (70,000 BTU/hr), Vertical Flame
• Insulation:
Test rated (optional)
5 
• UL 1685 / FT4, Vertical Tray Flame Test rated
123467
-
FR PVC Insulation
• ICEA T-30-520 (70,000 BTU/hr), Vertical Flame
rated: 60°C wet/ 105°C dry
Test rated
-
XLPE rated (optional)

• UV sunlight resistant “SUN RES” (all colours) -
VW-1 rated (optional)
• -40°C cold bend rated
Thermocouple Alloys
• Shielding (foil-free edge):
1. 
• Rated for use in hazardous locations:
FR PVC Insulated Thermocouple Alloy Wires - ISOS (standard)
2. 
- Class I Zone 2 (Div 2)
- OS (optional)
Individual Aluminum/Mylar Shielded Pairs with 3.
- Class II Zone 22 (Div 2)
Tinned Copper Drain Wire
• Armor:
Polypropylene Fillers
- Zetabon (optional)
4. 
Colour Coding
Polyester Separator Tape
• Jacket:
5. 
• Pairs - Red, Yellow - for KX type
- FR PVC yellow (standard) dependent on 
Overall Aluminum/Mylar Shield with Tinned 6.
• Pairs - Red,White - for JX type
Copper Drain Wire
requested thermocouple alloy
• Pairs - Red, Purple - for EX type
FR PVC Outer Protective Jacket
7.
rated: 90°C to -40°C 
• Pairs - Red, Black - for SX/RX type - Thermoset CPE (optional) 
• Pairs - Red, Orange - for NX type - Thermoplastic CPE (optional) 

• Pairs - Red, Blue - for NX type
-
Thermoplastic LSZH (optional)
• Available in:
- Composite constructions
- Custom insulation/jacket colors

- TC-ER (optional)
- Extension cables for type E, J, K, N, R, S and T
thermocouple alloys







Part Number
Number of Pairs
Conductor Size Nominal Diameter Overall Cable Weight (lb- Max. Pulling Tension Min. Bend Radius (Pull) 
(AWG/MCM)
cable (in/mm)
s/1000ft)/(kg/km)
(Pulling Eye) (lb/kg)
(in/mm)
7P021U160147700
1
16
0.257 / 6.53
40 / 60
41 / 19
4.6 / 118

7P022U160247700
7 / 178
2
16
0.389 / 9.88
91 / 135
82 / 37

8.5 / 216
7P022U160447700
4
16
0.472 / 11.99
145 / 216
165 / 75
7P022U160647700 10.1 / 256
6
16
0.561 / 14.24
206 / 307
247 / 112

10.9 / 277
7P022U160847700
8
16
0.607 / 15.41
257 / 383
330 / 150
7P022U161247700
13.6 / 346
12
16
0.756 / 19.2
381 / 567
494 / 224

19.1 / 484
7P022U162447700
24
16
1.059 / 26.9
720 / 1071
989 / 449
4.2 / 107
7P021U180147700
1
18
0.235 / 5.97
32 / 47
26 / 12

6.4 / 161
7P022U180247700
2
18
0.353 / 8.96
72 / 106
52 / 24
7.7 / 196
7P022U180447700
4
18
0.428 / 10.87
112 / 166
104 / 47

9.1 / 231
7P022U180647700
6
18
0.505 / 12.83
156 / 232
156 / 71
9.8 / 249
7P022U180847700
8
18
0.546 / 13.86
193 / 287
208 / 94

12.2 / 310
7P022U181247700
12
18
0.679 / 17.23
283 / 422
312 / 142
7P022U182447700
17 / 433
24
18
0.946 / 24.03
532 / 791
624 / 283












1 800 668 4842
shawcor.com
Pleasenote:Althoughthecontentusedforthisbrochurehasbeenproducedandprocessedfromsourcesbelievedtobereliable,nowarranty,expressedorimplied,ismaderegardingaccuracy,adequacy,completeness,legality,reliabilityorusefulnessofanyinformation