IEEE 1580 CONTROL | MULTI-CONDUCTOR (600V/1000V) 
PAGE 1 OF 1



ShawFlex IEEE 1580 Control cables are suitable for use in offshore oil and gas, shipboard and 

marine applications. Our cables are made to IEC speciications and can be modiied to it your 
speciic requirements.

Voltage
Certiications/Compliances

600/1000V
• IEEE 1580
• ASTM B8 (conductors)
Product Construction
4
• CSA FT4, Vertical Tray Flame Test rated
• Insulation: • IEC60332-3-22,CategoryAFlamePropagateTesting 1 2 3
5 6
- XLPE • American Bureau of Shipping
Armour:
• Transport Canada

- Tinned copper braid (optional)
• RoHS Compliant
- Bronze braid (optional)
• UV sunlight resistant “SUN RES” (all colours)
1. Bare Copper Conductors (Tinned Available) 
• Jacket:
• - 40°C cold bend rated
2. XLPE Insulated Conductors
3. Polypropylene Fillers
- FR PVC Inner/Outer Black Jacket • - 35°C cold impact rated
rated: 90°C (194°F) to -40°C (40°F)
4. Polyester Separator Tape
• Available in:
Colour Coding
5. Protective PVC Jacket
- Custom insulation/jacket colours
• As per IEEE 1580 Table 22





ShawFlex can manufacture up to 50 conductors in 0.75mm, 1.5mm, and 2.5mm
222


Part Number Number of Conductors Cross Section Nominal OD Overall Cable Cable Weight (lbs/1000ft)/(kg/km) Ampacity 
(AWG/MCM) (in/mm) (30°C ambient)

SY010M160200000 2 16 8.8 / 0.35 96 / 64 15

SY010M140200000 2 14 9.5 / 0.37 117 / 78 24

SY010M120200000 2 12 10.4 / 0.41 151 / 102 29

SY010M100200000 2 10 11.6 / 0.46 203 / 137 38
SY010M080200000 2 8 15.4 / 0.61 339 / 228 48

SY010M060200000 2 6 17.3 / 0.68 460 / 309 65

SY010M040200000 2 4 19.7 / 0.77 653 / 439 83
SY010M020200000 2 2 23.6 / 0.93 1006 / 676 111

SY010M010240000 2 1 26.6 / 1.05 1249 / 839 131

SY010M1/0240000 2 1/0 28.7 / 1.13 1512 / 1016 150

SY010M2/0240000 2 2/0 30.8 / 1.21 1831 / 1230 173
SY010M3/0240000 2 3/0 33.4 / 1.32 2230 / 1499 201

SY010M4/0240000 2 4/0 36.3 / 1.43 2728 / 1833 232

SY010M250260000 2 250 39.6 / 1.56 3179 / 2136 259
SY010M350260000 2 350 46.4 / 1.83 4454 / 2993 317

SY010M500260000 2 500 52.9 / 2.08 6101 / 4100 393

SY010M750260000 2 750 63.5 / 2.5 8945 / 6011 494

SY010M160300000 3 16 9.3 / 0.36 117 / 79 23
SY010M140300000 3 14 10 / 0.39 145 / 97 26

SY010M120300000 3 12 10.9 / 0.43 194 / 131 35

SY010M100300000 3 10 12.3 / 0.48 266 / 178 47
SY010M080300000 3 8 16.3 / 0.64 442 / 297 64

SY010M060300000 3 6 18.3 / 0.72 611 / 411 85

*Ampacity value based on National Electrical Code, Version 2011, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(16) for number of Conductors.