Page 15 - ShawFlex.com | Marine
P. 15


MARINE 


V.2 | 15
AWG



IEC POWER & CONTROL | MULTI-CONDUCTOR (600/1000V) 
PAGE 1 OF 2



ShawFlex IEC Power and Control cables are suitable for use in offshore oil and gas, shipboard 

and marine applications. Our cables are made to IEC speciications and can be modiied to it 
your speciic requirements.


Voltage
Certiications/Compliances
600/1000V
• IEC 60092-350
• IEC 60754-1
Product Construction
• IEC 61034-1&2
• Insulation:
• IEC60228 Class 5
35 
- XLPE (RW90 rated)
• IEC 60092-353, Control & Power
1246
rated: 90°C wet/dry, IEC 60092-351
• IEC 60092-376, Instrumentation
• Jacket:
• IEC60332-3-22,CategoryAFlamePropagateTesting 
- LSZH Thermoplastic, black (standard) • Lloyd’s Register
1. High Stranded Bare Copper Conductors 
rated: 75°C , SHF1 IEC 60092-359
• American Bureau of Shipping
(Tinned Available)
• Available in:
• Transport Canada
2. XLPE (RW90 Rated) Insulated Conductors
- Custom insulation/jacket colours
• RoHS Compliant
3. Polypropylene Fillers
• UV sunlight resistant “SUN RES” (all colours) 4. Fiberglass Tape
• - 40°C cold bend rated
5. Polyester Separator Tape
• - 35°C cold impact rated
6. Protective LSZH Jacket

Colour Coding
• 2C – Brown, blue

• 3C – Brown, black, grey
• 4C – Brown, black, grey, blue 
• 5C & higher– Black # Coded


Cross Section Nominal OD Overall Cable Cable Weight (lbs/1000ft)/ Ampacity 
Part Number Number of Conductors
(AWG/MCM) (in/mm) (kg/km) (45°C ambient)

SE010U160200800 2 16 9.07 / 0.36 109 / 73 20

SE010U140200800 2 14 9.73 / 0.38 130 / 87 22

SE010U120200800 2 12 10.64 / 0.42 165 / 111 30

SE010U100200800 2 10 12.17 / 0.48 227 / 153 39
SE010U080200800 2 8 13.64 / 0.54 313 / 210 54

SE010U060200800 2 6 15.77 / 0.62 440 / 295 73

SE010U040200800 2 4 18.92 / 0.75 657 / 442 97
SE010U020200800 2 2 22.12 / 0.87 970 / 652 128

SE010U010240800 2 1 24.61 / 0.97 1188 / 798 150

SE010U160300800 3 16 9.53 / 0.38 128 / 86 16

SE010U140300800 3 14 10.24 / 0.4 156 / 105 19
SE010U120300800 3 12 11.47 / 0.45 215 / 145 24

SE010U100300800 3 10 12.84 / 0.51 288 / 193 33

SE010U080300800 3 8 14.42 / 0.57 405 / 272 44
SE010U060300800 3 6 16.7 / 0.66 576 / 387 59

SE010U040300800 3 4 20.06 / 0.79 873 / 586 80

SE010U020300800 3 2 23.48 / 0.92 1311 / 881 106

SE010U010340800 3 1 26.41 / 1.04 1636 / 1099 123
SE010U160400800 4 16 10.32 / 0.41 148 / 99 16

SE010U140400800 4 14 11.11 / 0.44 190 / 128 19

SE010U120400800 4 12 12.47 / 0.49 260 / 175 24

SE010U100400800 4 10 14 / 0.55 359 / 241 33
*Ampacity value based on National Electrical Code, Version 2011, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(16) for number of Conductors.


1 800 668 4842 shawlex.com

Please note: Although the content used for this brochure has been produced and processed from sources believed to be reliable, no warranty, expressed or implied, is made regarding accuracy, adequacy, completeness, legality, reliability or usefulness of any information