AWG



IEC POWER & CONTROL | SINGLE CONDUCTOR (600/1000V) 
PAGE 1 OF 1



ShawFlex IEC Power and Control cables are suitable for use in offshore oil and gas, shipboard 

and marine applications. Our cables are made to IEC speciications and can be modiied to it 
your speciic requirements.


Voltage
Certiications/Compliances
600/1000V
• IEC 60092-350
• IEC 60754-1
Product Construction
• IEC 61034-1&2
• Insulation:
• EC 60228 Class 5
- XLPE (RW90 rated)
• IEC 60092-353, Control & Power 
1 2 3 
rated: 90°C wet/dry, 60092-351
• IEC 60092-376, Instrumentation
• Jacket:
• IEC60332-3-22,CategoryAFlamePropagateTesting 
- LSZH Thermoplastic, black (standard) • Lloyd’s Register
1.
High Strand Bare Copper Conductors (Tinned 
rated: 75°C , SHF1 IEC 60092-359
• American Bureau of Shipping
Available)
• Available in:
• Transport Canada
2. XLPE (RW90 Rated) Insulated Conductors 
- Custom insulation/jacket colours
• RoHS Compliant
3.
Protective LSZH Jacket
• UV sunlight resistant “SUN RES” (all colours) 
• - 40°C cold bend rated

• - 35°C cold impact rated

Colour Coding
• Black conductor (standard)






Cross Section Nominal OD Overall Cable Ampacity 
Part Number Number of Conductors Cable Weight (lbs/1000ft)/(kg/km) 
(AWG/MCM) (in/mm) (45°C ambient)

SE010U160100800 1 16 5.38 / 0.21 49 / 33 23

SE010U140100800 1 14 5.71 / 0.22 58 / 39 26

SE010U120100800 1 12 6.17 / 0.24 74 / 49 35

SE010U100100800 1 10 6.81 / 0.27 97 / 65 47
SE010U080100800 1 8 7.54 / 0.3 134 / 90 64

SE010U060100800 1 6 8.74 / 0.34 196 / 131 85

SE010U040100800 1 4 10.19 / 0.4 286 / 192 114
SE010U020100800 1 2 11.91 / 0.47 426 / 286 152

SE010U010140800 1 1 13.16 / 0.52 522 / 351 176

SE010U1/0140800 1 1/0 14.43 / 0.57 643 / 432 204

SE010U2/0140800 1 2/0 15.77 / 0.62 797 / 536 235
SE010U250160800 1 250 20.17 / 0.79 1420 / 954 357

SE010U350160800 1 350 23.7 / 0.93 1969 / 1323 432

SE010U500160800 1 500 27.41 / 1.08 2752 / 1849 541
SE010U600160800 1 600 30.28 / 1.19 3309 / 2223 580

SE010U750160800 1 750 33.07 / 1.3 4081 / 2742 667

*Ampacity value based on National Electrical Code, Version 2011, Table 3-10.15(B)(16). Values are corrected according to Table 310.15(B)(16) for number of Conductors.